SIPLUS S7-300 SM 336 F analog input modules - Safety Integrated Siemens

Область применения
The modules are used centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O device together with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH.
0 to 20 mA and 4 to 20 mA current transmitters (also HART) can be connected as encoders.
Обзор
F-AI HART analog input module for ET 200M
- Analog inputs for fail-safe SIPLUS S7 systems
- Applicable in the ET 200M distributed I/O device with IM 153-2 HF as well as centrally with SIPLUS S7-31xF-2 DP
- Properties of the SM 336; F-AI 6 x 0/4 ... 20 mA HART:
- 6 analog inputs with galvanic isolation between channels and backplane bus
- Input ranges: 0 mA to 20 mA, 4 mA to 20 mA
- Short-circuit proof power supply of 2 or 4-wire transmitter via the module
- External encoder supply possible
- Applicable in safety mode
- HART communication
- Firmware update using HW Config
- Identification data
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Дизайн
- 6 inputs for current measurement.
- Compact design:
- Group fault display (SF)
- Safety mode display (SAFE)
- Display for channel-specific faults (Fn)
- Display for HART status (Hn)
- Plug options for the 20-pin front connector, protected behind the front door.
- Labeling field on the front door.
- Easy assembly
Assembled like the other ET 200M I/O modules. - User-friendly wiring with 20-pin front connector.
Функции
The analog input module converts analog signals from the process to digital signals for internal processing by the fail-safe SIMATIC S7 CPUs.
The safety functions required for fail-safe operation are integrated in the module.
The following functions are available:
- Resolution 15 bits + sign.
- Measuring ranges:
- 0 to 20 mA or
- 4 to 20 mA or
- 4 to 20 mA (HART)
- Interrupt capability;
the module sends diagnostic interrupts to the CPU of the controller. - Diagnostics;
the module sends extensive diagnostic information to the CPU.
Технические данные
Order number | 6AG1336-4GE00-4AB0 | |
---|---|---|
SIPLUS S7-300 SM336 6AE F | ||
General information |
| |
Product type designation | SM 336 F-AI 6x0/4 to 20 mA HART | |
Supply voltage |
| |
Rated value (DC) | 24 V | |
Reverse polarity protection | Yes | |
Input current |
| |
From power supply L+, typ. | 150 mA | |
from backplane bus 5 V DC, max. | 90 mA | |
Power loss |
| |
Power loss, typ. | 4.5 W | |
Analog inputs |
| |
Number of analog inputs | 6 | |
permissible input current for current input (destruction limit), max. | 40 mA | |
Input ranges (rated values), currents |
| |
| Yes | |
| Yes | |
Cable length |
| |
| 1 000 m | |
Analog value generation for the inputs |
| |
Integration and conversion time/resolution per channel |
| |
| 16 bit; 15 bits + sign | |
| 20 ms @ 50 Hz, 16.7 ms @ 60 Hz | |
| f=n x (f1+-0.5%) | |
Encoder |
| |
Connection of signal encoders |
| |
| Yes | |
| Yes | |
Errors/accuracies |
| |
Operational error limit in overall temperature range |
| |
| 0.2 %; 40 µA | |
Basic error limit (operational limit at 25 °C) |
| |
| 0.1 % | |
Interrupts/diagnostics/status information |
| |
Alarms |
| |
| Yes | |
Diagnostic messages |
| |
| Yes | |
Potential separation |
| |
Potential separation analog inputs |
| |
| Yes | |
| Yes | |
| Yes | |
Isolation |
| |
Isolation tested with | 370V for 1 min | |
Standards, approvals, certificates |
| |
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Highest safety class achievable in safety mode |
| |
| 4 | |
| SIL 3 | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| 0 °C; = Tmin | |
| 60 °C; = Tmax | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity |
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance |
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method |
| |
required front connector | 20-pin | |
Dimensions |
| |
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights |
| |
Weight, approx. | 350 g |