FM 458-1 DP basic module Siemens

Область применения



The FM 458-1 DP basic module handles complete closed-loop control and computing tasks. Very short sampling times down to 100 µs even enable the handling of dynamic control tasks.

Обзор


  • Basic module for handling arithmetic, closed-loop control and open-loop control tasks
  • PROFIBUS DP interface for connection of distributed I/O and drives
  • Modular design with expansion modules for I/O and communication

Дизайн


  • 64-bit RISC processor for maximum computing performance
  • 8 fast digital inputs for level-controlled or edge-controlled calling of up to 8 alarm tasks (interrupts)
  • PROFIBUS DP interface for linking of distributed I/O and drive engineering
  • 256 KB SRAM with battery backup for fail-safe saving of up to 1000 process variables or recorded traces

EXM 438-1, EXM 448 and EXM 448-2 expansion modules

Expansion modules are available for the FM 458-1 DP basic module for fast signal transmission.

EXM 438-1: I/O expansion

  • Analog and digital inputs/outputs
  • Incremental and absolute encoder connections

EXM 448: communications expansion

  • PROFIBUS DP (master or slave) 1)
  • One slot for MASTERDRIVES option modules, e.g. for the SIMOLINK module SLB

EXM 448-2: communications expansion

  • 2 integral SIMOLINK connections

The expansion modules can only be used with the FM 458-1 DP, where max. two of these expansion modules can be freely combined.

Any number of these "FM 458-1 DP combinations" can be used in a SIMATIC S7-400 station taking into consideration the power consumptions.

Communication

Data exchange with the assigned SIMATIC CPU (according to configuration in HW Config) is implemented via the backplane bus which has been designed for fast data exchange.

Start-up and servicing using the online functions of STEP 7/CFC is carried out via the so-called C bus of the S77-400 station. It is then possible to start and diagnose the FM 458-1 DP e.g. via the central MPI connection of the SIMATIC CPU.

Communication with partners outside the S7-400 is preferably via the PROFIBUS DP interface present on the FM 458-1 DP basic module. This PROFIBUS DP interface offers the following properties:

  • Equidistance:
    The PROFIBUS DP cycle always has exactly the same length. This PROFIBUS DP cycle can be used as the start event for one of the eight interrupts. This permits synchronization of the user program with the PROFIBUS DP cycle.
  • Internode communication:
    The configured slaves can "directly" exchange data with one another without configuration in the FM 458-1 DP.
  • Routing capability:
    The slaves connected to this PROFIBUS DP interface can be parameterized and diagnosed by means of the integral C bus function via any other interfaces in the S7-400 system (e.g. the MPI interface integrated on the SIMATIC CPU) providing this is supported by the slaves, e.g. with MASTERDRIVES or DC-MASTER.
  • Configuration using HW Config:
    The configuration software is already integrated in STEP 7 (not an additional tool)

The EXM 448 communications expansion (see above) is available unchanged for compatibility reasons.

Accessories

  • SB10, SB61, SU12 interface modules with SC64 cable (for digital inputs).
  • Program memory modules.

1) Not equidistant or capable of internode communication; must be configured using COM PROFIBUS.

Функции



The configuration process is greatly simplified when floating-point arithmetic is used to solve control and computing tasks:

  • Normalization is not required.
  • Virtually unlimited range of values.
  • Very high resolution.

Configuration

Configuration instead of programming with CFC

The FM 458-1 DP is configured using the well-known software tools STEP 7 and CFC (Continuous Function Chart) which are also used to program the SIMATIC S7-400.

CFC is an intuitive Windows-based program that is easy to learn. The CFC has been expanded to include the function blocks and the optimized operating system using the D7-SYS add-on software package.

CFC noticeably reduces configuration time when used to create automation programs:

  • You can drag & drop function blocks from the block catalog; their inputs and outputs are then automatically connected. Subsequently, you only need to set the application-specific parameters to complete the configuration.
  • Detailed documentation automatically created
  • The interconnection of standard blocks is faster and less error-prone than programming
  • Frequently used program components (plans) can be transferred to a block that is reusable and can be centrally modified.
  • Hierarchical CFC plans increase transparency and improve the clarity of the program structure (plan-in-plan method or "top-down").
  • "CFC test mode" allows you to quickly execute a graphics-supported startup and trace signals on the screen while the system is running:
    • Viewing and editing values.
    • Entering, editing and deleting connections between function blocks.
    • Inserting or deleting function blocks.
  • With the user block generator, you can create individual function blocks in "C" for individual applications and also integrate them into the CFC.

Технические данные



Order number

6DD1607-0AA2

FM458-1 DP APPLICATION MODULE

Supply voltage

 

Rated value (DC)

  • 5 V DC

Yes

  • 24 V DC

Yes

permissible range (ripple included), lower limit (DC)

4.8 V

permissible range (ripple included), upper limit (DC)

5.25 V

Input current

 

Current consumption, typ.

1.5 A

Current consumption, max.

3 A

Memory

 

Backup

 

  • present

Yes; SRAM

Battery

 

Backup battery

 

  • Battery operation

Yes

  • Backup current, max.

15 µA

Hardware configuration

 

Slots

 

  • required slots

1

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

  • Resolution

500 ms

Digital inputs

 

Number of digital inputs

8; Connector X2

Input voltage

 

  • Rated value (DC)

24 V

  • for signal "0"

-1 to +6V

  • for signal "1"

13.5 to 33V

Input current

 

  • for signal "0", max. (permissible quiescent current)

0 mA

  • for signal "1", typ.

3 mA; at 24 V

Input delay (for rated value of input voltage)

 

for standard inputs

 

  • at "0" to "1", max.

5 µs

Interfaces

 

PROFIBUS DP

 

  • Equidistance

Yes; With connection to interrupt tasks

  • Direct data exchange (slave-to-slave communication)

Yes

Interrupts/diagnostics/status information

 

Alarms

 

  • Alarms

Yes

Potential separation

 

Potential separation digital inputs

 

  • Potential separation digital inputs

No; only via optional interface modules

Weights

 

Weight, approx.

1 000 g