SINAMICS G180 compact units Siemens

Обзор
The compact version of the SINAMICS G180 is a converter that can be combined very flexibly with the associated system components and integrated into customer-specific control cabinets or directly into machines.
Global use
SINAMICS G180 converter compact units are manufactured in compliance with relevant international standards and regulations, and are therefore suitable for global use (see technical data).
SINAMICS G180 compact unit
SINAMICS G180 converter compact units are available for the following voltages and power ratings:
Overview of voltages and power ratings for SINAMICS G180 compact units
Rated line voltage | Power |
---|---|
400 V 3 AC | 2.2 ... 160 kW |
500 V 3 AC | 2.2 ... 200 kW |
690 V 3 AC | 7.5 ... 200 kW |
Дизайн
- Rugged, compact aluminum enclosure
- IP20 degree of protection, optionally with IP21 protective top cover
- Convenient terminal compartment for EMC-compliant cable connections to NAMUR NE 37 in the device
- Complete touch protection in accordance with Employers'' Liability Association regulations (BGV A3)
- DC reactor fitted as standard to reduce harmonics, THD I 5th < 40 %
- dv/dt filter fitted as standard to reduce voltage peaks in the motor
Чертеж
Frame size K1
Main switch is integrated in the compact unit only with option S41.
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC15-5A7 | 2T2A-07400-002 |
6SE0100-1AC17-0A7 | 2T2A-07400-003 |
6SE0100-1AC21-0A7 | 2T2A-07400-004 |
6SE0100-1AC21-3A7 | 2T2A-07400-005 |
6SE0100-1AD14-5A7 | 2T2A-07500-002 |
6SE0100-1AD15-5A7 | 2T2A-07500-003 |
6SE0100-1AD17-0A7 | 2T2A-07500-004 |
6SE0100-1AD21-0A7 | 2T2A-07500-005 |
6SE0100-1AD21-3A7 | 2T2A-07500-007 |
Frame size K2
Main switch is integrated in the compact unit only with option S41.
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC21-8A7 | 2T2A-07400-007 |
6SE0100-1AC22-5A7 | 2T2A-07400-011 |
6SE0100-1AD21-8A7 | 2T2A-07500-011 |
6SE0100-1AD22-5A7 | 2T2A-07500-015 |
Frame size K3
Main switch is integrated in the compact unit only with option S41.
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC23-7A7 | 2T2A-07400-015 |
6SE0100-1AC24-8A7 | 2T2A-07400-022 |
6SE0100-1AC25-8A7 | 2T2A-07400-030 |
6SE0100-1AD23-7A7 | 2T2A-07500-022 |
6SE0100-1AD24-8A7 | 2T2A-07500-030 |
6SE0100-1AD25-8A7 | 2T2A-07500-037 |
6SE0100-1A21-0A7 | 2T2A-07600-007 |
6SE0100-1A21-3A7 | 2T2A-07600-011 |
6SE0100-1A21-8A7 | 2T2A-07600-015 |
6SE0100-1A22-5A7 | 2T2A-07600-022 |
Frame size K4
Main switch is integrated in the compact unit only with option S41.
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC27-8A7 | 2T2A-07400-037 |
6SE0100-1AC28-8A7 | 2T2A-07400-045 |
6SE0100-1AC31-1A7 | 2T2A-07400-055 |
6SE0100-1AD27-8A7 | 2T2A-07500-045 |
6SE0100-1AD28-8A7 | 2T2A-07500-055 |
6SE0100-1AD31-1A7 | 2T2A-07500-075 |
6SE0100-1A23-4A7 | 2T2A-07600-030 |
6SE0100-1A28-0A7 | 2T2A-07600-075 |
Frame size K5
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC31-5A7 | 2T2A-07400-075 |
6SE0100-1AC31-8A7 | 2T2A-07400-090 |
6SE0100-1AC32-1A7 | 2T2A-07400-110 |
6SE0100-1AD31-5A7 | 2T2A-07500-090 |
6SE0100-1AD31-8A7 | 2T2A-07500-110 |
6SE0100-1AD32-1A7 | 2T2A-07500-132 |
6SE0100-1A31-0A7 | 2T2A-07600-090 |
6SE0100-1A31-2A7 | 2T2A-07600-110 |
6SE0100-1A31-4A7 | 2T2A-07600-132 |
Frame size K51
Main switch is integrated as standard in compact units of frame size K51
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC31-5A7 +S41 | 2T2A-07400-075 |
6SE0100-1AC31-8A7 +S41 | 2T2A-07400-090 |
6SE0100-1AC32-1A7 +S41 | 2T2A-07400-110 |
6SE0100-1AD31-5A7 +S41 | 2T2A-07500-090 |
6SE0100-1AD31-8A7 +S41 | 2T2A-07500-110 |
6SE0100-1AD32-1A7 +S41 | 2T2A-07500-132 |
6SE0100-1A31-0A7 +S41 | 2T2A-07600-090 |
6SE0100-1A31-2A7 +S41 | 2T2A-07600-110 |
6SE0100-1A31-4A7 +S41 | 2T2A-07600-132 |
Frame size K6
SINAMICS G180 compact units | Converter type |
---|---|
6SE0100-1AC32-5A7 | 2T2A-07400-132 |
6SE0100-1AC33-0A7 | 2T2A-07400-160 |
6SE0100-1AD32-5A7 | 2T2A-07500-160 |
6SE0100-1AD33-0A7 | 2T2A-07500-200 |
6SE0100-1A31-7A7 | 2T2A-07600-160 |
6SE0100-1A32-1A7 | 2T2A-07600-200 |
Опции
The following tables provide an overview of the options and their availability for SINAMICS G180 compact units with a supply voltage of 400 V, 500 V or 690 V. (For details, see catalog chapter 4 "Option descriptions".)
|
| SINAMICS G180 compact units | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
| 400 V TN/TT system | 500 V IT system | 690 V TN/TT system | 690 V IT system | ||||||||||||
|
| Version – see selection and ordering data | |||||||||||||||
Option text | Additional ordering data -Z with order code and, if necessary, with plain text specification | A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P |
External control voltage supply | |||||||||||||||||
Connection for 230 V 1 AC 50 Hz control voltage provided by customer, without UPS backup | C56 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Connection for 230 V 1 AC 50 Hz control voltage provided by customer, with UPS backup | C57 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
RFI suppression filter | |||||||||||||||||
RFI suppression filter, category C2 or C3 (class A) | L00 | ❑ | ❑ | ❑ | ❑ | – | – | – | – | ❑ | ❑ | ❑ | ❑ | – | – | – | – |
RFI suppression filter, category C1 (class B) | L02 | ✓ | ✓ | ✓ | ✓ | – | – | – | – | – | – | – | – | – | – | – | – |
Line Harmonics Filter | |||||||||||||||||
Line Harmonics Filter for 50 Hz line frequency (supplied separately packed) | L03 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Line Harmonics Filter for 60 Hz line frequency up to 480 V (supplied separately packed) | L04 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Output filter | |||||||||||||||||
Strengthened dv/dt output filter for max. 250/300 m (type-dependent). Design for longer motor cables available on request | L10 | ✓ | ✓ | ✓ | ✓ | ❑ | ❑ | ❑ | ❑ | ❑ | ❑ | ✓1) | ✓1) | ❑ | ❑ | ✓1) | ✓1) |
Sine-wave filter IP00 for compact unit, suitable for motor frequencies of ≤ 75 Hz, voltage drop of approximately 5 % of line voltage (supplied separately packed) | L16 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Standard accessories packages | |||||||||||||||||
Main switch integrated into compact unit (might alter dimensions of unit) | S41 | ✓ | ✓ | ✓2) | – | ✓ | ✓ | ✓2) | – | ✓ | ✓ | ✓2) | – | ✓ | ✓ | ✓2) | – |
Braking chopper | |||||||||||||||||
Braking chopper integrated into converter (braking resistor is not included and must be ordered separately) | L72 | ❑ | ✓ | ✓ | ✓ | ❑ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Degrees of protection | |||||||||||||||||
Increased degree of protection IP21 for compact units | M21 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Other options | |||||||||||||||||
Board for mains supply backup | E85 | X | X | X | X | X | X | X | X | ❑ | ✓ | ✓ | ✓ | ❑ | ✓ | ✓ | ✓ |
External 4-line operator panel, supplied separately packed | K14 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Peripheral boards | |||||||||||||||||
Peripheral board 1 | G02 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Peripheral board 2 | G03 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Peripheral board 3 | G04 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Peripheral board 4 | G05 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Additional boards for bus connection | |||||||||||||||||
Board for PROFIBUS DPV1 | G01 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Board for CANopen | G20 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Board for Modbus RTU | G22 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Board for Modbus TCP | G27 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Accessories for IMS | |||||||||||||||||
USB PROFIBUS interface (supplied separately packed) | G13 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Ethernet-PROFIBUS gateway | G14 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Ethernet-to-RS232/485/422 converter (supplied separately packed) | G15 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
USB cable A/B (supplied separately packed) | G16 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Extension of the liability for defects | |||||||||||||||||
Extension of the liability for defects by 12 months as of commissioning date or by 24 months as of delivery date | Q80 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Extension of the liability for defects by 18 months as of commissioning date or by 30 months as of delivery date | Q81 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Extension of the liability for defects by 24 months as of commissioning date or by 36 months as of delivery date | Q82 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Extension of the liability for defects by 30 months as of commissioning date or by 42 months as of delivery date | Q83 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Extension of the liability for defects by 36 months as of commissioning date or by 48 months as of delivery date | Q84 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Extension of the liability for defects by 48 months as of commissioning date or by 60 months as of delivery date | Q85 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Label for plant identification | |||||||||||||||||
Cabinet designation TAG/ITEM number according to ordering data | T01 | ✓ | ✓ | ✓ | ✓ | ✓ | Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |