SINAMICS G180 cabinet units - liquid-cooled Siemens

Дизайн
Protection against condensation
With liquid-cooled units, warm air can condense on the cold surfaces of the pipes and heat sink. This condensation depends on the air humidity and the temperature difference between the ambient air and the coolant. The higher the humidity level, the smaller the temperature difference at which condensate will form. The water which is produced as a result of condensation can cause corrosion as well as electrical damage such as creepage shorts and flashovers. The solenoid valve (-Y1) integrated in the converter regulates the coolant temperature according to the temperature of the ambient air and thus effectively protects the unit against condensation.
Closed cooling circuit for a SINAMICS G180 liquid-cooled converter
The following diagram shows a typical example of a closed cooling circuit with an explanation of all the main cooling circuit components.
SINAMICS G180 liquid-cooled cabinet unit – recommended layout for a closed cooling circuit
Open cooling circuit for a SINAMICS G180 liquid-cooled converter
The following diagram shows a typical example of an open cooling circuit with an explanation of all the main cooling circuit components.
SINAMICS G180 liquid-cooled cabinet unit – recommended layout for an open cooling circuit
Чертеж
Frame size SW2
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑1BA33‑7❑A7 | 2T6A‑77401‑200 |
6SE0170‑1BA34‑6❑A7 | 2T6A‑77401‑250 |
6SE0170‑1BA36‑3❑A7 | 2T6A‑77401‑315 |
6SE0170‑1BD33‑7❑A7 | 2T6A‑77501‑250 |
6SE0170‑1BD34‑6❑A7 | 2T6A‑77501‑315 |
6SE0170‑1BD36‑0❑A7 | 2T6A‑77501‑400 |
6SE0170‑1B❑33‑2❑A7 | 2T6A‑77601‑250 |
6SE0170‑1B❑33‑6❑A7 | 2T6A‑77601‑315 |
6SE0170‑1B❑34‑2❑A7 | 2T6A‑77601‑400 |
Frame size SW21
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑1BA37‑3❑A7 | 2T6A‑77401‑400 |
6SE0170‑1BD37‑3❑A7 | 2T6A‑77501‑500 |
6SE0170‑1B❑35‑2❑A7 | 2T6A‑77601‑500 |
Frame size SW3
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑1BA38‑8❑A7 | 2T6A‑77401‑500 |
6SE0170‑1BA41‑0❑A7 | 2T6A‑77401‑560 |
6SE0170‑1BA41‑1❑A7 | 2T6A‑77401‑630 |
6SE0170‑1BD38‑2❑A7 | 2T6A‑77501‑560 |
6SE0170‑1BD38‑8❑A7 | 2T6A‑77501‑630 |
6SE0170‑1BD41‑0❑A7 | 2T6A‑77501‑710 |
6SE0170‑1BD41‑1❑A7 | 2T6A‑77501‑800 |
6SE0170‑1B❑35‑7❑A7 | 2T6A‑77601‑560 |
6SE0170‑1B❑36‑4❑A7 | 2T6A‑77601‑630 |
6SE0170‑1B❑37‑1❑A7 | 2T6A‑77601‑710 |
6SE0170‑1B❑37‑7❑A7 | 2T6A‑77601‑800 |
6SE0170‑1B❑41‑0❑A7 | 2T6A‑77601‑909 |
6SE0170‑1B❑41‑1❑A7 | 2T6A‑77601‑910 |
Frame size SW4
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑1C❑41‑2❑A7 | 2T6A‑77602‑912 |
6SE0170‑1C❑41‑3❑A7 | 2T6A‑77602‑913 |
6SE0170‑1C❑41‑5❑A7 | 2T6A‑77602‑915 |
6SE0170‑1C❑41‑7❑A7 | 2T6A‑77602‑917 |
6SE0170‑1C❑42‑0❑A7 | 2T6A‑77602‑919 |
6SE0170‑2CH41‑2❑A7 | 2T6F‑77602‑912 |
6SE0170‑2CH41‑3❑A7 | 2T6F‑77602‑913 |
6SE0170‑2CH41‑5❑A7 | 2T6F‑77602‑915 |
6SE0170‑2CH41‑7❑A7 | 2T6F‑77602‑917 |
6SE0170‑2CH42‑0❑A7 | 2T6F‑77602‑919 |
Frame size SW5
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑2BA33‑7❑A7 | 2T6F‑77401‑200 |
6SE0170‑2BA34‑6❑A7 | 2T6F‑77401‑250 |
6SE0170‑2BA36‑3❑A7 | 2T6F‑77401‑315 |
6SE0170‑2BA37‑3❑A7 | 2T6F‑77401‑400 |
6SE0170‑2BD33‑7❑A7 | 2T6F‑77501‑250 |
6SE0170‑2BD34‑6❑A7 | 2T6F‑77501‑315 |
6SE0170‑2BD36‑3❑A7 | 2T6F‑77501‑400 |
6SE0170‑2BD37‑3❑A7 | 2T6F‑77501‑500 |
6SE0170‑2BH33‑2❑A7 | 2T6F‑77601‑250 |
6SE0170‑2BH33‑6❑A7 | 2T6F‑77601‑315 |
6SE0170‑2BH34‑2❑A7 | 2T6F‑77601‑400 |
6SE0170‑2BH35‑2❑A7 | 2T6F‑77601‑500 |
Frame size SW6
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑2BA38‑8❑A7 | 2T6F‑77401‑500 |
6SE0170‑2BA41‑0❑A7 | 2T6F‑77401‑560 |
6SE0170‑2BA41‑1❑A7 | 2T6F‑77401‑630 |
6SE0170‑2BD38‑2❑A7 | 2T6F‑77501‑560 |
6SE0170‑2BD38‑8❑A7 | 2T6F‑77501‑630 |
6SE0170‑2BD41‑0❑A7 | 2T6F‑77501‑710 |
6SE0170‑2BD41‑1❑A7 | 2T6F‑77501‑800 |
6SE0170‑2BH35‑7❑A7 | 2T6F‑77601‑560 |
6SE0170‑2BH36‑4❑A7 | 2T6F‑77601‑630 |
6SE0170‑2BH37‑1❑A7 | 2T6F‑77601‑710 |
6SE0170‑2BH37‑7❑A7 | 2T6F‑77601‑800 |
6SE0170‑2BH41‑0❑A7 | 2T6F‑77601‑909 |
6SE0170‑2BH41‑1❑A7 | 2T6F‑77601‑910 |
Frame size SW7
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑2DH42‑2❑A7 | 2T6F‑77603‑920 |
6SE0170‑2DH42‑4❑A7 | 2T6F‑77603‑923 |
6SE0170‑2DH42‑7❑A7 | 2T6F‑77603‑926 |
6SE0170‑2DH43‑0❑A7 | 2T6F‑77603‑929 |
6SE0170‑3DH42‑2❑A7 | 2T6K‑77603‑920 |
6SE0170‑3DH42‑4❑A7 | 2T6K‑77603‑923 |
6SE0170‑3DH42‑7❑A7 | 2T6K‑77603‑926 |
6SE0170‑3DH43‑0❑A7 | 2T6K‑77603‑929 |
Frame size SW8
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑2EH43‑2❑A7 | 2T6F‑77604‑931 |
6SE0170‑2EH43‑6❑A7 | 2T6F‑77604‑935 |
6SE0170‑2EH44‑0❑A7 | 2T6F‑77604‑939 |
Frame size SW9
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑4CH41‑2❑A7 | 2T6L‑77602‑912 |
6SE0170‑4CH41‑3❑A7 | 2T6L‑77602‑913 |
6SE0170‑4CH41‑5❑A7 | 2T6L‑77602‑915 |
6SE0170‑4CH41‑7❑A7 | 2T6L‑77602‑917 |
6SE0170‑4CH42‑0❑A7 | 2T6L‑77602‑919 |
Frame size SW10
Dimensional drawing applies to standard converters without options. The cabinet dimensions might change if options are selected.
SINAMICS G180 cabinet units, liquid-cooled | Converter type |
---|---|
6SE0170‑4EH43‑2❑A7 | 2T6L‑77604‑931 |
6SE0170‑4EH43‑6❑A7 | 2T6L‑77604‑935 |
6SE0170‑4EH44‑0❑A7 | 2T6L‑77604‑939 |