Central plant clocks Siemens

Обзор



The central plant clocks evaluate the clock time data that was transmitted from the wireless receiver and generate diverse output signals in order to synchronize the connected I/O devices.

If the wireless receiver fails or signal transmission is interrupted, the central plant clocks switch over to their internal high-precision quartz system and thus ensure reliable tracking of the clock time. When the input signal is available again, the central plant clock adjusts any time differences that may have occurred without time jumps by means of "microsteps".

SICLOCK TC100 and SICLOCK TC400 central plant clocks

Inputs and outputs

The high-precision SICLOCK TC100 and SICLOCK TC400 central plant clocks have one (SICLOCK TC100) or two (SICLOCK TC400) inputs for connection to wireless receivers.

The central plant clocks have one (SICLOCK TC100) or four (SICLOCK TC400) independent 10/100 Mbit Ethernet interfaces.

The network stations are synchronized using the proven SNTP standard and by means of the SIMATIC procedure.

The SICLOCK central plant clocks have two relay outputs for signaling alarms or warnings.

Alternatively and/or in addition, two point-to-point connections TTY (20 mA current interface) or one RS 422 (5 V level) connection can be set up for the SICLOCK TC400 central plant clock.

Operation

Parameterization of the interfaces, setting of the signal types, redundancy modes, and read-out of the status messages stored in the device are conveniently implemented via the integrated web interface.

LEDs and a display indicate operating states and show any error messages, which can also be read out via the web interface.

Note:

In order to use the comfort-parameterization , you have to use a personal computer with the software Java Runtime V1.4.0 or later version from Oracle. This software is not included in the scope of delivery, but has to be acquired separately, which may incur additional cost.

Технические данные



Order number

 

2XV9450-2AR22

2XV9450-2AR01

product brand name

 

SICLOCK

Product designation

 

Central plant clock

Product type designation

 

TC100

TC400

General technical data:

 

 

 

Supply voltage at DC

V

24

Relative positive tolerance of the supply voltage

%

20

Relative negative tolerance of the supply voltage

%

15

Buffering time in the event of power failure maximum

ms

3

Continuous current Rated value maximum

A

0.5

0.7

Operating current of fuse protection at input slow-blow

A

1

Active power consumption maximum

W

9

15

Active power loss typical

W

6

7.5

Protection class IP

 

IP20

Operating resource protection class

 

III (according to EN 60536)

Time deviation

 

 

 

  • relating to DCF77 signal maximum

µs

1 000

  • relating to GPS signal maximum

µs

50

Relative accuracy

 

 

 

  • with loss of DCF77 signal maximum

%

0.000001

  • on loss of GPS signal maximum

%

0.0001

  • in the event of power failure maximum

%

0.0004

Clock error compensation relating to 1 s in micro-steps

µs

50

Time deviation of the GPS signal with jitter maximum

ns

200

Protocol is supported

 

(S)NTP, DCF77

(S)NTP, DCF77, pulses, cycles, message frames

Battery life

 

 

 

  • during operation minimum

y

10

12

  • unconnected during storage minimum

y

10

12

  • connected during storage maximum

y

6

Standards:

 

 

 

Standard for EMC

 

EN 55022 Class A, FCC Class, EN 55024

Standard

 

 

 

  • for environmental influences during storage

 

EN 60721-3-2 class 2K4

  • for environmental influences during operation

 

EN 60721-3-3 class 3KS

Standard for relative humidity

 

 

 

  • for environmental influences during operation

 

IEC 60068-2-78, IEC 60068-2-30

  • for environmental influences during storage

 

IEC 60068-2-78, IEC 60068-2-30

Ambient conditions:

 

 

 

Ambient temperature

 

 

 

  • during transport

°C

-40 ... +70

  • during storage

°C

-40 ... +70

  • during operation

°C

0 ... 65

Temperature change of the ambient temperature relating to one hour without condensation

 

 

 

  • during operation

°C

10

  • during storage

°C

20

Relative humidity at 25 °C without condensation

 

 

 

  • during storage

%

10 ... 95

  • during operation

%

10 ... 95

Air pressure

hPa

1 080 ... 795

Installation altitude

m

2 000 ... -1 000

Inputs/ Outputs:

 

 

 

Number of interfaces acc. to Industrial Ethernet

 

1

4

Transfer rate for Industrial Ethernet

Mbit/s

10 ... 100

Galvanic isolation between Ethernet and electronics

 

Yes

Product function at the Ethernet interface Autonegotiation

 

Yes

Input version for clock time

 

1x GPS1000 / DCFRS time input 48 V / 40 mA

2x GPS1000 / DCFRS time input 48 V / 40 mA

Output version for supply of the antenna

 

20 mA to 40 mA at 48 V

Number of interfaces as output

 

 

 

  • acc. to RS 422

1

1

  • acc. to 20 mA (TTY)

1

2

Number of relay outputs as NC contact

 

 

 

  • for ALARM

1

1

  • for WARNING

1

1

Ampacity of the relay outputs at DC at 48 V

A

0.06

Installation/ mounting/ dimensions:

 

 

 

Mounting type

 

DIN rail 35 mm or 19 inch rack

Width

mm

180

Height

mm

89

Depth

mm

47


Дальнейшая информация



For further product details, refer to the