IM 151-8 PN/DP CPU Siemens

Область применения



The IM 151-8 PN/DP CPU can be used for remote, distributed automation solutions with average programming complexity. It enables remote preprocessing of the process data on site and only transmits required data to the higher-level control unit. This results in the following advantages:

  • Relieves the central control unit
  • Short response times to critical signals on site
  • Low data volume relieves bus system
  • Pretested units and parallel commissioning enable faster set-up
  • Autonomous machine units increase availability and flexibility
  • Clear configuration processes

The IM 151-8 PN/DP CPU operates completely independent of the central control unit. If it fails, the IM 151-8 PN/DP CPU simply continues to run.

The bit-modular design of the ET 200S I/O system together with the IM 151-8 PN/DP CPU enable functionally oriented station design.

Обзор


  • Interface module for SIMATIC ET 200S with integrated CPU S7-314
  • For high-performance control solutions in ET 200S
  • Increase of the availability of systems and machines
  • PROFINET IO Controller for up to 128 IO Devices
  • PROFINET I-Device for connecting the CPU as an intelligent PROFINET device under a SIMATIC or non-Siemens PROFINET IO controller
  • PROFINET interface with integrated 3-port switch
  • Isochronous mode on PROFINET
  • With many communication options: PG/OP communication, PROFINET IO, PROFINET CBA, open IE communication (TCP, ISO-on-TCP and UDP), web server and S7-communication (with loadable FBs)
  • Fast, simple and end-to-end programming of a system with modular programs via STEP 7
  • Compact SIMATIC Micro Memory Card (MMC)
  • Optional PROFIBUS master for 32 PROFIBUS DP slaves (with master interface 6ES7138-4HA00-0AB0)
  • Fail-safe IM 151-8F PN/DP CPU PROFIsafe available

Note:
SIMATIC Micro Memory Card required for operation of CPU.

Дизайн



The IM 151-8 PN/DP CPU features the following:

  • Microprocessor; execution time 60 ns per binary instruction
  • 192 KB RAM
  • Bit-modular expandability for maximum flexibility; up to 63 I/O modules (power, electronic, technology and motor starter modules) in any combination
  • PROFINET interface with 3 integrated switch ports (RJ45)
  • A password concept protects the user program from unauthorized access
  • Block encryption: By means of S7 Block Privacy, the functions (FCs) and function blocks (FBs) can be stored in the CPU in encrypted form to protect the know-how of the application.
  • Diagnostics buffer for the last 500 errors and interrupt events (the last 100 entries are retentive)
  • SIMATIC MMC
    • Program backup (load memory)
    • Firmware update using MMC
    • External load memory on MMC
  • For maintenance-free data backup without battery
  • Update via MMC or online update via networks
  • Hardware clock; date and time can be appended to diagnostic messages of the CPU
  • Integrated communication functions:
    • PG/OP communication
    • PROFINET IO
    • Open IE communication (TCP, ISO-on-TCP and UDP)
    • Web server
    • PROFINET CBA
    • S7 communication (with loadable FBs)
    • Routing
    • Data set routing
  • Alarm response time (OB40) less than 10 ms

Функции



Configurable and programmable properties

  • I/O setup: Type and scope
  • General: Defining the name, plant designation, and location designation
  • Start-up Defining the startup characteristics of the CPU and the monitoring time
  • Synchronous cycle interrupts: Setting the IO system number, process image partition number, and delay time
  • Cycle/clock memory: startup and cycle characteristics: Defining the maximum cycle time and load as well as self-test functions. Setting the clock memory address
  • Retentivity: Definition of the number of retentive bit memories, counters, timers and data blocks
  • Time-of-day interrupts: Setting the start date, start time, and periodicity of clock memories: Address setting
  • Cyclic interrupts: Setting of periodicity
  • System diagnostics: Definition of the handling and scope of diagnostic messages
  • Protection level: Specifying the access rights to programs and data
  • Communication: Reserving the connection resources
  • Web: Settings for the Web server of the CPU
  • Parameters: Setting the module parameters for the entire ET 200S station
  • PROFINET interface: Setting the addresses. Parameterizing the PROFINET properties, the I-Device functionality on PROFINET, the time synchronization using the NTP procedure, the media redundancy, and the KeepAlive function
  • Parameterizing Port 1, Port 2 and Port 3

Display and information functions

  • Status and error functions; LEDs indicate, for example, hardware, programming, time or I/O errors, as well as operating states such as RUN, STOP, restart, etc.
  • Test functions; the PG is used to indicate signal status during program execution, to modify process variables independently of the user program and to output the contents of stack memories
  • Information functions; you can use the programming device to obtain information about the storage capacity and operating mode of the CPU as well as the current utilization of the main and load memories, current cycle times and diagnostic buffer contents in plain text

Programming, parameterization

The ET 200S with IM 151-8 PN/DP CPU can be programmed, configured and diagnosed with STEP 7 system-wide from any point in the network.

Технические данные



Order number

6ES7151-8AB01-0AB0

ET200S, IM151-8 PN/DP CPU, 192 KB

General information

 

Engineering with

 

  • Programming package

STEP7 V 5.5 or higher

Supply voltage

 

Rated value (DC)

  • 24 V DC

Yes

Power loss

 

Power loss, typ.

5.5 W

Memory

 

Work memory

 

  • integrated

192 kbyte

  • Size of retentive memory for retentive data blocks

64 kbyte

Load memory

 

  • Plug-in (MMC), max.

8 Mbyte

CPU processing times

 

for bit operations, typ.

0.06 µs

for word operations, typ.

0.12 µs

for fixed point arithmetic, typ.

0.16 µs

for floating point arithmetic, typ.

0.59 µs

Counters, timers and their retentivity

 

S7 counter

 

  • Number

256

IEC counter

 

  • present

Yes

S7 times

 

  • Number

256

IEC timer

 

  • present

Yes

Data areas and their retentivity

 

Flag

 

  • Number, max.

256 byte

Address area

 

I/O address area

 

  • Inputs

2 048 byte

  • Outputs

2 048 byte

Process image

 

  • Inputs, adjustable

2 048 byte

  • Outputs, adjustable

2 048 byte

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

Operating hours counter

 

  • Number

1

1. Interface

 

Interface type

PROFINET

Physics

Ethernet

Number of ports

3; RJ45

Functionality

 

  • MPI

No

  • DP master

No

  • DP slave

No

  • PROFINET IO Controller

Yes; Also simultaneously with IO-Device functionality

  • PROFINET IO Device

Yes; Also simultaneously with IO Controller functionality

  • PROFINET CBA

Yes

  • Point-to-point connection

No

PROFINET IO Controller

 

  • Number of connectable IO Devices for RT, max.

128

  • Number of IO Devices with IRT and the option "high flexibility"

128

  • Number of IO Devices with IRT and the option "high performance", max.

64

2. Interface

 

Interface type

External interface via master module 6ES7138-4HA00-0AB0

Physics

RS 485

Functionality

 

  • MPI

No

  • DP master

Yes

  • DP slave

No

  • PROFINET IO Controller

No

  • PROFINET IO Device

No

  • PROFINET CBA

No

DP master

 

  • Number of DP slaves, max.

32; Per station

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

No

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes; With DP master module

Global data communication

 

  • supported

No

S7 basic communication

 

  • supported

Yes; I blocks

S7 communication

 

  • supported

Yes

Open IE communication

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

8

  • ISO-on-TCP (RFC1006)

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

8

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

8

Web server

 

  • supported

Yes

Number of connections

 

  • overall

12

Programming

 

Programming language

 

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes; Optional

  • CFC

Yes; Optional

  • GRAPH

Yes; Optional

  • HiGraph®

Yes; Optional

Know-how protection

 

  • User program protection/password protection

Yes

  • Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

120 mm; DP master module: 35 mm

Height

119.5 mm

Depth

75 mm

Weights

 

Weight, approx.

320 g; DP master module: Approx. 100 g