LZS, LZX Coupling Relays, Plug-In Siemens

Обзор



Coupling relays with plug-in relays can be ordered as complete units or as individual modules for customer assembly.

Function

The coupling relays with semiconductor outputs have a low power consumption and are therefore particularly well suited for solid-state systems. In the versions equipped with LEDs, these indicate the switching state.

The LZS:PT/MT coupling relays have a test button. Thus, the relays can be forced into the switching state and locked without electrical control. This is indicated by a raised petrol-colored lever.

Control with solid-state output

In the case of solid-state outputs (e. g. proximity switch) with overload and short-circuit protection, you must make allowance during configuration for the temporarily flowing capacitor charging currents! This is possible, for example, by using a suitable LZS coupling relay with plug-in relay.

Surge suppression

The 24 V DC relays LZX:RT and LZX: PT with LEDs can be supplied with, all others without integral surge suppression (freewheel diode connected in parallel with A1/A2). The positive control supply voltage must be connected to coil terminal A1.

Mounting

The relays are plugged into the base and this is snapped onto a TH 35 standard mounting rail according to IEC 60715.

A retaining bracket can be ordered for the MT series that additionally fixes the relay into a plug-in base (under conditions of increased mechanical stress). For the RT and PT series, a combined fixing and ejection bracket is available which can be used to disassemble the relay where access is difficult, for example, when relays are mounted side-by-side.

They can be mounted as required.

Logical separation

The terminals for the contacts and the terminals for the coil are arranged on separate levels, e. g. above for contacts and below for coil. Logical separation is not necessarily safe isolation.

Protective separation

For safe isolation, transfer of the voltage from one circuit to another circuit is prevented to a suitable degree of safety (requirements and tests are described in IEC 60947‑1 in Appendix N).

Notes on the previous LZX series

The complete units and accessory parts in the LZX series are no longer listed in this catalog. Complete units in the LZS series are fully compatible with the corresponding units in the LZX series. At the same time prices for the LZS series are lower than for the previous LZX series.

The LZX series plug-in relays are still available, and are used accordingly in both the LZS and the LZX series.

Note:

Due to differences in geometry, the LED modules, plug-in bases, retaining brackets and labels can be combined and/or used only in the respective series, LZS or LZX.

The LZS series offers not only service-proven screw connections but also versions with plug-in terminals (push-in).