SIPLUS master interface modules for IM 151 CPU Siemens

Область применения
The master interface module adds a DP master interface to the IM 151-7(F-)CPU / IM 151-8(F) PN/DP CPU. A lower-level PROFIBUS DP line can thus be established. This results in the following advantages:
- Offloading of the central controller by means of distributed preprocessing
- IM 151-7 (F-)CPU / IM 151-8(F) PN/DP CPU is possible as DP master in stand-alone mode
- Use of the CPU in hierarchical networks, e.g. with IE/PB Link also on Ethernet (CBA, etc.)
Обзор
PROFIBUS DP master interface module for interface module IM 151-7 (R) CPU / IM 151-8 (F) PN/DP CPU
- Integrated 12 Mbit/s PROFIBUS DP master interface in Cu version
- Allows parallel operation of two PROFIBUS DP interfaces on one IM 151-7 CPU
- Allows operation of one PROFIBUS DP interface with an IM 151-8 (F) PN/DP CPU
- Increase in availability of systems and machines
- Functionality in accordance with a DP master configured interface of an S7-314 CPU
Programming is performed with STEP 7 from version V5.2 with Service Pack 1.
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
SIPLUS master interface module for IM 151 CPU | |
Article No. | 6AG1 138-4HA00-7AB0 |
BasedOn Article No. | 6ES7 138-4HA00-0AB0 |
Ambient temperature range | -25 °C … +70 °C |
Conformal coating | Coating of the printed circuit boards and the electronic components |
Technical data | The technical data of the standard product applies except for the ambient conditions. |
Ambient conditions | |
Relative humidity | 100%, condensation/frost permitted. No commissioning in bedewed state. |
Biologically active substances, compliance with EN 60721-3-3 | Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! |
Chemically active substances, compliance with EN 60721-3-3 | Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! |
Mechanically active substances, compliance with EN 60721-3-3 | Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Air pressure (depending on the highest positive temperature range specified) | 1 080 ... 795 hPa (-1 000 … +2 000 m) See ambient temperature range 795 ... 658 hPa (+2 000 ... +3 500 m) derating 10 K |
For technical documentation on SIPLUS, see: