Basic Line Modules Siemens

Обзор
Basic Line Modules are available for applications in which no energy is returned to the supply or where the energy exchange between motor and generator axes takes place in the DC link. The connected Motor Modules are pre-charged via the thyristor gate control. Basic Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.
A Braking Module of the appropriate frame size can be integrated into a Basic Line Module in order to permit, in conjunction with an external braking resistor, regenerative operation of the drive system (→ DC link components).
Дизайн
The Basic Line Modules have the following interfaces as standard:
- 1 line supply connection
- 1 connection for the 24 V DC electronics power supply
- 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
- 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
- 3 DRIVE-CLiQ sockets
- 1 temperature sensor input (KTY84-130, PTC or Pt100)
- 1 PE/protective conductor connection
The status of the Basic Line Modules is indicated via two multicolor LEDs.
The scope of supply of the Basic Line Modules includes:
- DRIVE-CLiQ cable for connecting to a CU320-2 or SIMOTION D4x5 Control Unit
- DRIVE-CLiQ cable to connect the Control Unit to the first Motor Module
Интеграция
The Basic Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate Basic Line Modules.
Connection example of a Basic Line Module
Технические данные
General technical specifications
Electrical specifications | |
---|---|
Line power factor | |
| > 0.96 |
| 0.75 … 0.93 |
Efficiency | > 99 % |
DC link voltage, approx. 1) | 1.35 × line voltage under partial load |
Main contactor control | |
| 240 V AC, max. 8 A |
Conformity | CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC) |
Approvals, according to | cULus (only for drive units connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC) |
1) The DC link voltage is unregulated and load-dependent. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 380 … 480 V 3 AC | Basic Line Modules | |||||
---|---|---|---|---|---|---|
| 6SL3330-1TE34-2AA3 | 6SL3330-1TE35-3AA3 | 6SL3330-1TE38-2AA3 | 6SL3330-1TE41-2AA3 | 6SL3330-1TE41-5AA3 | |
Rated power | ||||||
| kW | 200 | 250 | 400 | 560 | 710 |
| kW | 160 | 200 | 315 | 450 | 560 |
| hp | 305 | 385 | 615 | 860 | 1090 |
| hp | 245 | 305 | 485 | 690 | 860 |
DC link current | ||||||
| A | 420 | 530 | 820 | 1200 | 1500 |
| A | 328 | 413 | 640 | 936 | 1170 |
| A | 630 | 795 | 1230 | 1800 | 2250 |
Input current | ||||||
| A | 365 | 460 | 710 | 1010 | 1265 |
| A | 547 | 690 | 1065 | 1515 | 1897 |
Current demand | ||||||
| A | 1.1 | 1.1 | 1.1 | 1.1 | 1.1 |
DC link capacitance | ||||||
| μF | 7200 | 9600 | 14600 | 23200 | 29000 |
| μF | 57600 | 76800 | 116800 | 185600 | 232000 |
Power loss, max. 2) | ||||||
| kW | 1.9 | 2.1 | 3.2 | 4.6 | 5.5 |
| kW | 1.9 | 2.1 | 3.2 | 4.6 | 5.5 |
Cooling air requirement | m3/s | 0.17 | 0.17 | 0.17 | 0.36 | 0.36 |
Sound pressure level LpA (1 m) at 50/60 Hz | dB | 66/68 | 66/68 | 66/68 | 71/73 | 71/73 |
Line supply connection U1, V1, W1 |
| M10 screw | M10 screw | M10 screw | 3 × M12 screw | 3 × M12 screw |
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 6 × 185 | 6 × 185 |
DC link connection DCP, DCN |
| M10 screw | M10 screw | M10 screw | 3 × hole for M12 | 3 × hole for M12 |
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 6 × 185 | 6 × 185 |
PE/GND connection |
| 2 × hole for M10 | 2 × hole for M10 | 2 × hole for M10 | 2 × hole for M12 | 2 × hole for M12 |
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 4 × 240 | 4 × 240 |
Cable length, max. 3) | ||||||
| m | 2600 | 2600 | 2600 | 4000 | 4000 |
| m | 3900 | 3900 | 3900 | 6000 | 6000 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 |
Dimensions | ||||||
| mm | 310 | 310 | 310 | 310 | 310 |
| mm | 1164 | 1164 | 1164 | 1653 | 1653 |
| mm | 352 | 352 | 352 | 550 | 550 |
Weight, approx. | kg | 96 | 96 | 96 | 214 | 214 |
Frame size |
| FB | FB | FB | GB | GB |
1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.
2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
3) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 … 690 V 3 AC | Basic Line Modules | |||||
---|---|---|---|---|---|---|
| 6SL3330-1TG33-0AA3 | 6SL3330-1TG34-3AA3 | 6SL3330-1TG36-8AA3 | 6SL3330-1TG41-1AA3 | 6SL3330-1TG41-4AA3 | |
Rated power | ||||||
| kW | 250 | 355 | 560 | 900 | 1100 |
| kW | 195 | 280 | 440 | 710 | 910 |
| kW | 175 | 250 | 390 | 635 | 810 |
| kW | 165 | 235 | 365 | 595 | 755 |
| hp | 250 | 350 | 600 | 900 | 1250 |
| hp | 200 | 300 | 450 | 800 | 1000 |
DC link current | ||||||
| A | 300 | 430 | 680 | 1100 | 1400 |
| A | 234 | 335 | 530 | 858 | 1092 |
| A | 450 | 645 | 1020 | 1650 | 2100 |
Input current | ||||||
| A | 260 | 375 | 575 | 925 | 1180 |
| A | 390 | 563 | 863 | 1388 | 1770 |
Current demand | ||||||
| A | 1.1 | 1.1 | 1.1 | 1.1 | 1.1 |
DC link capacitance | ||||||
| μF | 3200 | 4800 | 7300 | 11600 | 15470 |
| μF | 25600 | 38400 | 58400 | 92800 | 123760 |
Power loss, max. 2) | ||||||
| kW | 1.5 | 2.1 | 3.0 | 5.4 | 5.8 |
| kW | 1.5 | 2.1 | 3.0 | 5.4 | 5.8 |
Cooling air requirement | m3/s | 0.17 | 0.17 | 0.17 | 0.36 | 0.36 |
Sound pressure level LpA (1 m) at 50/60 Hz | dB | 66/68 | 66/68 | 66/68 | 71/73 | 71/73 |
Line supply connection U1, V1, W1 |
| M10 screw | M10 screw | M10 screw | 3 × M12 screw | 3 × M12 screw |
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 6 × 185 | 6 × 185 |
DC link connection DCP, DCN |
| M10 screw | M10 screw | M10 screw | 3 × M12 screw | 3 × M12 screw |
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 6 ×185 | 6 × 185 |
PE/GND connection |
| 2 × hole M10 | 2 × hole M10 | 2 × hole M10 | 2 × hole M12 | 2 × hole M12 |
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 4 × 240 | 4 × 240 |
Cable length, max. 3) | ||||||
| m | 1500 | 1500 | 1500 | 2250 | 2250 |
| m | 2250 | 2250 | 2250 | 3375 | 3375 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 |
Dimensions | ||||||
| mm | 310 | 310 | 310 | 310 | 310 |
| mm | 1164 | 1164 | 1164 | 1653 | 1653 |
| mm | 352 | 352 | 352 | 550 | 550 |
Weight, approx. | kg | 96 | 96 | 96 | 214 | 214 |
Frame size |
| FB | FB | FB | GB | GB |
1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.
2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
3) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.