Smart Line Modules are line-commutated infeed/regenerative units with 100 % continuous regenerative power that are immune to inverter commutation faults. The regenerative capability of the modules can be deactivated by means of parameterization.
Smart Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.
The DC link is pre-charged by means of integrated pre-charging resistors.
To operate the Smart Line Module, the associated line reactor or a suitable transformer is required.
Дизайн
The Smart Line Modules have the following interfaces as standard:
- 1 line supply connection
- 1 connection for the 24 V DC electronics power supply
- 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
- 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
- 3 DRIVE-CLiQ sockets
- 1 temperature sensor input (KTY84-130, PTC or Pt100)
- 1 PE/protective conductor connection (2 connections for sizes HX and JX)
The status of the Smart Line Modules is indicated via two multi-color LEDs.
The scope of supply of the Smart Line Modules includes:
- DRIVE-CLiQ cable to connect to a CU320-2 or SIMOTION D4x5 Control Unit
- DRIVE-CLiQ cable to connect the Control Unit to the first Motor Module
Интеграция
The Smart Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit.
Connection example of a Smart Line Module
Технические данные
General technical specifications
Electrical specifications | |
---|---|
Line power factor | |
| > 0.96 |
| 0.75 … 0.93 |
Efficiency | > 98.5 % |
DC link voltage, approx. 1) | 1.32 × line voltage under partial load |
Bypass contactor control | |
| 240 V AC, max. 8 A |
Conformity | CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC) |
Approvals, according to | cULus (only for drive units connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC) |
1) The DC link voltage is unregulated and load-dependent. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 380 … 480 V 3 AC | Smart Line Modules | |||||
---|---|---|---|---|---|---|
| 6SL3330-6TE35-5AA3 | 6SL3330-6TE37-3AA3 | 6SL3330-6TE41-1AA3 | 6SL3330-6TE41-3AA3 | 6SL3330-6TE41-7AA3 | |
Rated power | ||||||
| kW | 250 | 355 | 500 | 630 | 800 |
| kW | 235 | 315 | 450 | 555 | 730 |
| hp | 385 | 545 | 770 | 970 | 1230 |
| hp | 360 | 485 | 695 | 855 | 1125 |
DC link current | ||||||
| A | 550 | 730 | 1050 | 1300 | 1700 |
| A | 490 | 650 | 934 | 1157 | 1513 |
| A | 825 | 1095 | 1575 | 1950 | 2550 |
Infeed/regenerative feedback current | ||||||
| A | 463 | 614 | 883 | 1093 | 1430 |
| A | 694 | 921 | 1324 | 1639 | 2145 |
Current demand | ||||||
| A | 1.35 | 1.35 | 1.4 | 1.5 | 1.7 |
| A | 1.8 | 1.8 | 3.6 | 5.4 | 5.4 |
DC link capacitance | ||||||
| μF | 8400 | 12000 | 16800 | 18900 | 28800 |
| μF | 42000 | 60000 | 67200 | 75600 | 115200 |
Power loss, max. 2) | ||||||
| kW | 3.7 | 4.7 | 7.1 | 11 | 11.5 |
| kW | 3.7 | 4.7 | 7.1 | 11 | 11.5 |
Cooling air requirement | m3/s | 0.36 | 0.36 | 0.78 | 1.08 | 1.08 |
Sound pressure level LpA (1 m) at 50/60 Hz | dB | 69/73 | 69/73 | 70/73 | 70/73 | 70/73 |
Line supply connection U1, V1, W1 |
| M10 screw | M10 screw | 2 × M12 screw | 3 × M12 screw | 3 × M12 screw |
| mm2 | 2 × 240 | 2 × 240 | 4 × 240 | 6 × 240 | 6 × 240 |
DC link connection DCP, DCN |
| M10 screw | M10 screw | 4 × hole for M12 | 4 × hole for M12 | 4 × hole for M12 |
| mm2 | 2 × 240 | 2 × 240 | Busbar | Busbar | Busbar |
PE/GND connection |
| Hole for M10 | Hole for M10 | – | – | – |
| mm2 | 2 × 240 | 2 × 240 | – | – | – |
PE1/GND connection |
| – | – | M12 screw | M12 screw | M12 screw |
| mm2 | – | – | 240 | 240 | 240 |
PE2/GND connection |
| – | – | 2 × M12 screw | 2 × M12 screw | 2 × M12 screw |
| mm2 | – | – | 2 × 240 | 2 × 240 | 2 × 240 |
Cable length, max. 3) | ||||||
| m | 4000 | 4000 | 4800 | 4800 | 4800 |
| m | 6000 | 6000 | 7200 | 7200 | 7200 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 |
Dimensions | ||||||
| mm | 310 | 310 | 503 | 704 | 704 |
| mm | 1413 | 1413 | 1475 | 1480 | 1480 |
| mm | 550 | 550 | 548 | 550 | 550 |
Weight, approx. | kg | 150 | 150 | 294 | 458 | 458 |
Frame size |
| GX | GX | HX | JX | JX |
1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.
2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.
3) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 … 690 V 3 AC | Smart Line Modules | ||||
---|---|---|---|---|---|
| 6SL3330-6TG35-5AA3 | 6SL3330-6TG38-8AA3 | 6SL3330-6TG41-2AA3 | 6SL3330-6TG41-7AA3 | |
Rated power | |||||
| kW | 450 | 710 | 1000 | 1400 |
| kW | 405 | 665 | 885 | 1255 |
| kW | 320 | 525 | 705 | 995 |
| kW | 295 | 480 | 640 | 910 |
| hp | 500 | 790 | 1115 | 1465 |
| hp | 450 | 740 | 990 | 1400 |
DC link current | |||||
| A | 550 | 900 | 1200 | 1700 |
| A | 490 | 800 | 1068 | 1513 |
| A | 825 | 1350 | 1800 | 2550 |
Infeed/regenerative feedback current | |||||
| A | 463 | 757 | 1009 | 1430 |
| A | 694 | 1135 | 1513 | 2145 |
Current demand | |||||
| A | 1.35 | 1.4 | 1.5 | 1.7 |
| A | 1.3 | 2.9 | 4.3 | 4.3 |
| A | 0.94 | 2.1 | 3.1 | 3.1 |
DC link capacitance | |||||
| μF | 5600 | 7400 | 11100 | 14400 |
| μF | 28000 | 29600 | 44400 | 57600 |
Power loss, max. 2) | |||||
| kW | 4.3 | 6.5 | 12.0 | 13.8 |
| kW | 4.3 | 6.5 | 12.0 | 13.8 |
Cooling air requirement | m3/s | 0.36 | 0.78 | 1.08 | 1.08 |
Sound pressure level LpA (1 m) at 50/60 Hz | dB | 69/73 | 70/73 | 70/73 | 70/73 |
Line supply connection U1, V1, W1 |
| M10 screw | 2 × M12 screw | 3 × M12 screw | 3 × M12 screw |
| mm2 | 2 × 240 | 4 × 240 | 6 × 240 | 6 × 240 |
DC link connection DCP, DCN |
| M10 screw | 4 × hole for M12 | 4 × hole for M12 | 4 × hole for M12 |
| mm2 | 2 × 240 | Busbar | Busbar | Busbar |
PE connection |
| Hole for M10 | – | – | – |
| mm2 | 2 × 240 | – | – | – |
PE1/GND connection |
| – | M12 screw | M12 screw | M12 screw |
| mm2 | – | 240 | 240 | 240 |
PE2/GND connection |
| – | 2 × M12 screw | 2 × M12 screw | 2 × M12 screw |
| mm2 | – | 2 × 240 | 2 × 240 | 2 × 240 |
Cable length, max. 3) | |||||
| m | 2250 | 2750 | 2750 | 2750 |
| m | 3375 | 4125 | 4125 | 4125 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 |
Dimensions | |||||
| mm | 310 | 503 | 704 | 704 |
| mm | 1413 | 1475 | 1480 | 1480 |
| mm | 550 | 548 | 550 | 550 |
Weight, approx. | kg | 150 | 294 | 458 | 458 |
Frame size |
| GX | HX | JX | JX |
1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.
2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
3) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.