Smart Line Modules Siemens

Обзор



Smart Line Modules are line-commutated infeed/regenerative units with 100 % continuous regenerative power that are immune to inverter commutation faults. The regenerative capability of the modules can be deactivated by means of parameterization.

Smart Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.

The DC link is pre-charged by means of integrated pre-charging resistors.

To operate the Smart Line Module, the associated line reactor or a suitable transformer is required.

Дизайн



The Smart Line Modules have the following interfaces as standard:

  • 1 line supply connection
  • 1 connection for the 24 V DC electronics power supply
  • 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
  • 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
  • 3 DRIVE-CLiQ sockets
  • 1 temperature sensor input (KTY84-130, PTC or Pt100)
  • 1 PE/protective conductor connection (2 connections for sizes HX and JX)

The status of the Smart Line Modules is indicated via two multi-color LEDs.

The scope of supply of the Smart Line Modules includes:

  • DRIVE-CLiQ cable to connect to a CU320-2 or SIMOTION D4x5 Control Unit
  • DRIVE-CLiQ cable to connect the Control Unit to the first Motor Module

Интеграция



The Smart Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit.

Connection example of a Smart Line Module

Технические данные



General technical specifications

Electrical specifications

Line power factor
at rated power

 
  • Basic fundamental (cos ϕ1)

> 0.96

  • Total (λ)

0.75 … 0.93

Efficiency

> 98.5 %

DC link voltage, approx. 1)

1.32 × line voltage under partial load
1.30 × line voltage under full load

Bypass contactor control

 
  • Terminal block -X9/5-6

240 V AC, max. 8 A
30 V DC, max. 1 A

Conformity

CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC)

Approvals, according to

cULus (only for drive units connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)



1) The DC link voltage is unregulated and load-dependent. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 380 … 480 V 3 AC

Smart Line Modules

 

6SL3330-6TE35-5AA3

6SL3330-6TE37-3AA3

6SL3330-6TE41-1AA3

6SL3330-6TE41-3AA3

6SL3330-6TE41-7AA3

Rated power

      
  • For IN DC (50 Hz 400 V)

kW

250

355

500

630

800

  • For IH DC (50 Hz 400 V)

kW

235

315

450

555

730

  • For IN DC (60 Hz 460 V)

hp

385

545

770

970

1230

  • For IH DC (60 Hz 460 V)

hp

360

485

695

855

1125

DC link current

      
  • Rated current IN DC

A

550

730

1050

1300

1700

  • Base load current IH DC 1)

A

490

650

934

1157

1513

  • Maximum current Imax DC

A

825

1095

1575

1950

2550

Infeed/regenerative feedback current

      
  • Rated current IN E

A

463

614

883

1093

1430

  • Maximum current Imax E

A

694

921

1324

1639

2145

Current demand

      
  • 24 V DC auxiliary power supply

A

1.35

1.35

1.4

1.5

1.7

  • 400 V AC

A

1.8

1.8

3.6

5.4

5.4

DC link capacitance

      
  • Smart Line Module

μF

8400

12000

16800

18900

28800

  • Drive line-up, max.

μF

42000

60000

67200

75600

115200

Power loss, max. 2)

      
  • At 50 Hz 400 V

kW

3.7

4.7

7.1

11

11.5

  • At 60 Hz 460 V

kW

3.7

4.7

7.1

11

11.5

Cooling air requirement

m3/s

0.36

0.36

0.78

1.08

1.08

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

69/73

69/73

70/73

70/73

70/73

Line supply connection

U1, V1, W1

 

M10 screw

M10 screw

2 × M12 screw

3 × M12 screw

3 × M12 screw

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

2 × 240

4 × 240

6 × 240

6 × 240

DC link connection

DCP, DCN

 

M10 screw

M10 screw

4 × hole for M12

4 × hole for M12

4 × hole for M12

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

2 × 240

Busbar

Busbar

Busbar

PE/GND connection

 

Hole for M10

Hole for M10

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

2 × 240

PE1/GND connection

 

M12 screw

M12 screw

M12 screw

  • Conductor cross-section, max. (IEC)

mm2

240

240

240

PE2/GND connection

 

2 × M12 screw

2 × M12 screw

2 × M12 screw

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

2 × 240

2 × 240

Cable length, max. 3)

      
  • Shielded

m

4000

4000

4800

4800

4800

  • Unshielded

m

6000

6000

7200

7200

7200

Degree of protection

 

IP00

IP00

IP00

IP00

IP00

Dimensions

      
  • Width

mm

310

310

503

704

704

  • Height

mm

1413

1413

1475

1480

1480

  • Depth

mm

550

550

548

550

550

Weight, approx.

kg

150

150

294

458

458

Frame size

 

GX

GX

HX

JX

JX



1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

3) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 500 … 690 V 3 AC

Smart Line Modules

 

6SL3330-6TG35-5AA3

6SL3330-6TG38-8AA3

6SL3330-6TG41-2AA3

6SL3330-6TG41-7AA3

Rated power

     
  • For IN DC (50 Hz 690 V)

kW

450

710

1000

1400

  • For IH DC (50 Hz 690 V)

kW

405

665

885

1255

  • For IN DC (50 Hz 500 V)

kW

320

525

705

995

  • For IH DC (50 Hz 500 V)

kW

295

480

640

910

  • For IN DC (60 Hz 575 V)

hp

500

790

1115

1465

  • For IH DC (60 Hz 575 V)

hp

450

740

990

1400

DC link current

     
  • Rated current IN DC

A

550

900

1200

1700

  • Base load current IH DC 1)

A

490

800

1068

1513

  • Maximum current Imax DC

A

825

1350

1800

2550

Infeed/regenerative feedback current

     
  • Rated current IN E

A

463

757

1009

1430

  • Maximum current Imax E

A

694

1135

1513

2145

Current demand

     
  • 24 V DC auxiliary power supply

A

1.35

1.4

1.5

1.7

  • 500 V AC

A

1.3

2.9

4.3

4.3

  • 690 V AC

A

0.94

2.1

3.1

3.1

DC link capacitance

     
  • Smart Line Module

μF

5600

7400

11100

14400

  • Drive line-up, max.

μF

28000

29600

44400

57600

Power loss, max. 2)

     
  • At 50 Hz 690 V

kW

4.3

6.5

12.0

13.8

  • At 60 Hz 575 V

kW

4.3

6.5

12.0

13.8

Cooling air requirement

m3/s

0.36

0.78

1.08

1.08

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

69/73

70/73

70/73

70/73

Line supply connection

U1, V1, W1

 

M10 screw

2 × M12 screw

3 × M12 screw

3 × M12 screw

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

4 × 240

6 × 240

6 × 240

DC link connection

DCP, DCN

 

M10 screw

4 × hole for M12

4 × hole for M12

4 × hole for M12

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

Busbar

Busbar

Busbar

PE connection

 

Hole for M10

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

PE1/GND connection

 

M12 screw

M12 screw

M12 screw

  • Conductor cross-section, max. (IEC)

mm2

240

240

240

PE2/GND connection

 

2 × M12 screw

2 × M12 screw

2 × M12 screw

  • Conductor cross-section, max. (IEC)

mm2

2 × 240

2 × 240

2 × 240

Cable length, max. 3)

     
  • Shielded

m

2250

2750

2750

2750

  • Unshielded

m

3375

4125

4125

4125

Degree of protection

 

IP00

IP00

IP00

IP00

Dimensions

     
  • Width

mm

310

503

704

704

  • Height

mm

1413

1475

1480

1480

  • Depth

mm

550

548

550

550

Weight, approx.

kg

150

294

458

458

Frame size

 

GX

HX

JX

JX



1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

3) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.