SIMATIC Microbox PC Siemens

Обзор



Продукция для SIMATIC PCS 7 V8.0 из этой секции будет доступна позднее и впоследствии будет обновлена.

Соответствующие продукты для SIMATIC PCS 7 V7.1 ищите в разделе "Предыдущие версии".

Технические данные



Comparison of SIMATIC PCS 7 OS Clients 427D and 477D

SIMATIC PCS7 OS Clients based on Microbox

Types

SIMATIC PCS 7 OS Client 427D

SIMATIC PCS 7 OS Client 477D

Design and equipment features

  

Design

  • Compact Microbox PC without panel
  • DIN rail or wall mounting; horizontal (preferred) or vertical
  • Portrait mounting; vertical
  • Compact Panel PC, consisting of 22" TFT Touch Panel with integrated computing unit
  • Built-in unit for installation in mounting cutouts, e.g. in consoles or cabinets; in landscape format (vertical or max. ± 45° vertical incline)
  • Fastening with mounting clips or mounting brackets

Degree of protection in accordance with IEC 60529

IP20

IP65 front; IP20 rear (enclosure)

CPU

  
  • Processor

Intel Core i7-3517UE 1.7 GHz

Intel Core i7-3517UE 1.7 GHz

  • Second Level Cache

4 MB

4 MB

Main memory (module up to 8 GB operable without/with ECC)

4 GB DDR3-SDRAM 1066 (1 SO‑DIMM module without ECC)

4 GB DDR3-SDRAM 1066 (1 SO‑DIMM module without ECC)

Graphic

  
  • Graphic controller

Intel HD4000 integrated in the chipset

Intel HD4000 integrated in the chipset

  • Graphics memory

32 ... 512 MB shared memory

32 ... 512 MB shared memory

  • Resolutions/frequencies (digital)
  
  • DVI-I

Up to 1920 × 1200, 60 Hz

Up to 1920 × 1200, 60 Hz

  • Display port (DPP)

Up to 1920 × 1200, 60 Hz

Up to 1920 × 1200, 60 Hz

  • Color display

22" Touch Panel with LED backlight

  • Resolution

1920 × 1080, 24-bit colors

  • Half brightness lifetime

30 000 h

Storage media, alternative

  
  • Hard disk

1 × 2.5" SATA-HDD 320 GB

1 × 2.5" SATA-HDD 320 GB

  • Solid State Drive

1 × 2.5" SATA-SSD 160 GB (eMLC)

1 × 2.5" SATA-SSD 160 GB (eMLC)

Storage media, additive

  
  • CD-ROM/DVD‑RW/diskette

Connectable via USB (not included in scope of delivery)

Connectable via USB (not included in scope of delivery)

Interfaces

  
  • Ethernet

2 × Ethernet interfaces (RJ45) Intel 82579LM and Intel 82574L; 10/100/1000 Mbps, isolated, teaming-capable

2 × Ethernet interfaces (RJ45) Intel 82579LM and Intel 82574L; 10/100/1000 Mbps, isolated, teaming-capable

  • USB

4 × USB 3.0 rear, max. 2 × high-current can be operated simultaneously

4 × USB 3.0 rear, max. 2 × high-current can be operated simultaneously

1 × USB 2.0 front, high current

  • Serial

1 × COM1 RS 232, 115 Kbps max., 9-pin D-sub connector

1 × COM1 RS 232, 115 Kbps max., 9-pin D-sub connector

  • Parallel

  • Graphics connection

1 × DVI-I (DVI/VGA combined)

1 × display port (DPP); DVI via DPP-to-DVI adapter

1 × DVI-I (DVI/VGA combined)

1 × display port (DPP); DVI via DPP-to-DVI adapter

  • Keyboard, mouse

Connectable via USB (keyboard and mouse not included in scope of delivery)

Connectable via USB (keyboard and mouse not included in scope of delivery)

LED displays

  • PC ON/WD for power supply and watchdog
  • L1, L2 and L3 freely programmable by the user

Operating system, basic software

  

Operating system

Windows 7 Ultimate SP1, 64-bit, multi-language (English, German, French, Italian, Spanish, Chinese)

Windows 7 Ultimate SP1, 64-bit, multi-language (English, German, French, Italian, Spanish, Chinese)

System-tested SIMATIC industrial software

SIMATIC IPC DiagMonitor integrated in pre-installation

SIMATIC IPC DiagMonitor integrated in pre-installation

Monitoring and diagnostics functions

  

Watchdog

  • Monitoring of program execution
  • Restart can be parameterized following faults
  • Monitoring time adjustable in the software
  • Monitoring of program execution
  • Restart can be parameterized following faults
  • Monitoring time adjustable in the software

Temperature

  • Processor
  • Basic module
  • Close to RAM

(via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management)

  • Processor
  • Basic module
  • Close to RAM

(via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management)

Storage media

S.M.A.R.T. functionality

S.M.A.R.T. functionality

Battery monitoring

Status readable via battery status register; remaining life after reaching the warning level at least 1 month

Status readable via battery status register; remaining life after reaching the warning level at least 1 month

Operating hours counter

(via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management)

(via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management)

Noise emission

  

Operating noise

< 40 dB (A) according to DIN 45635‑1

< 40 dB (A) according to DIN 45635‑1

Electromagnetic compatibility (EMC)

  

Interference emission

EN 61000‑6‑3, EN 61000‑6‑4, CISPR220 Class B;

FCC Class A

EN 61000-6-4; CISPR 22 Class A;

FCC Class A

Immunity to conducted interference on the supply cables

±2 kV (according to IEC 61000-4‑4; burst)

±1 kV (according to IEC 61000-4‑5; symmetrical surge)

±2 kV (according to IEC 61000-4‑5; asymmetrical surge)

±2 kV (according to IEC 61000-4‑4; burst)

±1 kV (according to IEC 61000-4‑5; symmetrical surge)

±2 kV (according to IEC 61000-4‑5; asymmetrical surge)

Noise immunity on signal cables

±1 kV (according to IEC 61000-4‑4; burst; length < 3 m)

±2 kV (according to IEC 61000-4‑4; burst; length > 3 m)

±2 kV (according to IEC 61000-4‑5; surge; length > 30 m)

±1 kV (according to IEC 61000-4‑4; burst; length < 3 m)

±2 kV (according to IEC 61000-4‑4; burst; length > 3 m)

±2 kV (according to IEC 61000-4‑5; surge; length > 30 m)

Immunity to static discharge in accordance with IEC 61000-4-2

±6 kV contact discharge

±8 kV air discharge

±6 kV contact discharge at front

±4 kV contact discharge at enclosure rear

±8 kV air discharge

Immunity to radio frequency interference

10 V/m, 80 ... 1 000 MHz and 1.4 ... 2 GHz, 80 % AM to IEC 61000‑4‑3

1 V/m, 2 ... 2.7 GHz, 80 % AM to IEC 61000‑4‑3

10 V, 10 kHz ... 80 MHz, 80 % AM to IEC 61000‑4‑6

10 V/m, 80 ... 1 000 MHz, 80 % AM to IEC 61000‑4‑3

1 V/m, 2 ... 2.7 GHz

3 V/m, 2 ... 2.7 GHz

10 V, 10 kHz ... 80 MHz to IEC 61000‑4‑6

Immunity to magnetic fields

100 A/m, 50/60 Hz according to IEC 61000‑4‑8

100 A/m, 50/60 Hz according to IEC 61000‑4‑8

Climatic conditions

 

Temperature

Tested according to IEC 60068‑2‑1, IEC 60068‑2‑2, IEC 60068‑2‑14

Tested according to IEC 60068‑2‑1, IEC 60068‑2‑2

  • Horizontal mounting, in operation (427D only)
  
  • Operation with hard disk and max. 2 expansion modules (max. load 10 W)

+5 ... +40 °C1)

  • Operation with SSD and max. 2 expansion modules (max. load 10 W)

0 … +40 °C

  • Operation with SSD in RAL2) and max. 2 expansion modules (max. load 10 W)

0 ... +50 °C1)

  • Vertical mounting/portrait mounting, in operation (427D only)
  
  • Operation with hard disk (without expansion module)

+5 ... +35 °C1)

  • Operation with SSD (without expansion module)

0 … +40 °C

  • Operation with SSD in RAL2) and max. 2 expansion modules (max. load 10 W)

0 … +45 °C1)

  • Mounting in landscape format, vertical (477D only)
  
  • Operation with hard disk

+5 ... +40 °C

  • Operation with SSD

0 … +45 °C

  • Mounting in landscape format, vertical incline max. ±45 ° (477D only)
  
  • Operation with hard disk

+5 ... +35 °C

  • Operation with SSD

0 … +40 °C

  • Storage/transport
  
  • HDD

-40 … +60 °C

-20 … +60 °C

  • SSD

-40 … +70 °C

-20 … +60 °C

  • Gradient
  
  • Operation

Max. 10 °C/h

  • Storage

20 °C/h; no condensation

20 °C/h; no condensation

Relative humidity

Tested according to IEC 60068‑2‑78, IEC 60068‑2‑30

Tested according to IEC 60068‑2‑78, IEC 60068‑2‑30

  • Operation

5 ... 80 % at 25 °C (no condensation)

5 ... 85 % at 30 °C (no condensation)

  • Storage/transport

5 ... 95 % at 25 °C (no condensation)

5 ... 95 % at 25 °C (no condensation)

Air pressure

Tested according to IEC 60068-2-13

Tested according to IEC 60068-2-13

  • Operation

1080 ... 795 hPa, corresponds to an altitude of ‑1000 … 2000 m

1080 ... 795 hPa, corresponds to an altitude of ‑1000 … 2000 m

  • Storage/transport

1080 ... 660 hPa, corresponds to an altitude of ‑1000 … 3500 m

1080 ... 660 hPa, corresponds to an altitude of ‑1000 … 3500 m

Mechanical environmental conditions

  

Vibrations

Tested according to IEC 60068‑2‑6

Tested according to IEC 60068‑2‑6

  • Operation
  
  • With SSD

5 … 9 Hz: 3.5 mm

9 … 500 Hz: 9.8 m/s²

5 … 8.4 Hz: 3.5 mm

8.4 … 500 Hz: 9.8 m/s²

  • With hard disk and wall mounting (427D) or installation (477D)

10 … 58 Hz: 0.0375 mm
58 ... 200 Hz: 4.9 m/s²

10 … 58 Hz: 0.375 mm

58 ... 200 Hz: 4.9 m/s²

  • With hard disk and DIN rail mounting or vertical mounting (427D)

Starting prohibited

  • Storage/transport

5 … 9 Hz: 3.5 mm

9 … 500 Hz: 9.8 m/s²

5 … 8.4 Hz: 3.5 mm

8.4 … 500 Hz: 9.8 m/s²

Shock resistance

Tested according to IEC 60068‑2‑27

Tested according to IEC 60068‑2‑27, IEC 60068‑2‑29

  • Operation

Without hard disk: 150 m/s², 11 ms

With hard disk: 50 m/s², 30 ms

50 m/s², 30 ms

  • Storage/transport

250 m/s², 6 ms

250 m/s², 6 ms

Standards, specifications, approvals

  

CE according to 2004/108/EC, 2006/95/EC

Yes

Yes

Industrial area of application

  
  • Interference emission

EN 61000-6-4: 2007

EN 61000-6-4: 2007

  • Immunity to interference

EN 61000-6-2: 2005

EN 61000-6-2: 2005

Application in apartments, business, trade, small enterprises

  
  • Interference emission

EN 61000-6-3: 2007

  • Immunity to interference

EN 61000-6-1: 2007

cUlus

Underwriters Laboratories (UL) according to standard UL 60950‑1 and UL 508 as well as Canadian National Standard CAN/CSA-C22.2 No. 60950-1 (I.T.E) and CAN/CSA-C22.2 No. 142 (IND.CONT.EQ)

Underwriters Laboratories (UL) according to standard UL 508 and Canadian National Standard CAN/CSA-C22.2 No. 142 (IND.CONT.EQ)

USA: FCC Rules, Part 15, Class A

Yes

Yes

Canada: ICES-003, Class A; NMB‑003, Class A

Yes

Yes

Australia/New Zealand: EN 61000-6-4:2007

Yes

Yes

Korea: Korean Certification (KC Mark)

Yes

Yes

Special features

  

Quality assurance

According to ISO 9001

According to ISO 9001

Power supply (electrically isolated)

  

Supply voltage

24 V DC (19.2 ... 28.8 V)

24 V DC (19.2 ... 28.8 V)

Short-term voltage interruption

Min. 15 ms (at 20.4 V)

Max. 10 events per hour; recovery time of at least 1 s

Min. 20 ms

Max. 10 events per hour; recovery time of at least 1 s

Max. power consumption (at 24 V DC)

64.8 W

74 W

Dimensions and weights

  

External dimensions (W × H × D in mm)

262 × 133 × 50.5

560 × 380 × 84

Mounting cutout (W × H in mm)

540 × 360

Mounting depth (D in mm)

75.5

Weight

Approx. 2 kg

Approx. 7 kg



1) If the "Turbo Mode Level" setting in the BIOS Setup "Power" menu is not set to "Temperature optimized", the maximum ambient temperature must be reduced by 5 °C.