Smart Line Modules Siemens

Обзор



Smart Line Modules are uncontrolled rectifier/regenerative units. The infeed circuit comprises a diode bridge, while the line-commutated regenerative feedback circuit with immunity to inverter commutation faults comprises IGBTs with 100 % continuous regenerative power. An autotransformer is not required for regenerative feedback.

The regenerative capability can be deactivated with a digital input.

Smart Line Modules are suitable for connection to grounded TN/TT and non-grounded IT systems. The following voltages and power ratings are available:

Line voltage

Rated power

80 … 480 V 3 AC 

250 … 800 kW

500 … 690 V 3 AC

450 … 1400 kW



The power ratings can be increased by connecting up to four identical Smart Line Modules in parallel. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Дизайн



IGBTs (fundamental frequency-switched) serve as Smart Line Module power semiconductors. Because this reduces switching losses, a high percentage of the power unit current can be utilized.

The current flows in rectifier direction via the freewheeling diodes of the IGBTs. This means that the Smart Line Module behaves in a similar way to the Basic Line Module. If the DC link voltage increases due to regenerative operation of the drives, the IGBTs conduct the current, thus feeding the energy back into the supply system.

In contrast to Active Line Modules, Smart Line Modules do not require a line-side filter; all they require is a line reactor (4 % uk). The unit has a built-in pre-charging circuit for the DC link capacitors. For this reason, a line contactor or a motor-driven circuit breaker is absolutely essential. By specifying the option with order code L44 for the Line Connection Modules, these components are appropriately accommodated in the Line Connection Module.

Parallel connection of Smart Line Modules to increase power rating

Up to four Smart Line Modules with the same power rating can be connected in parallel in order to increase power. Current derating of 7.5 % with respect to the rated current of each Smart Line Module must be taken into account when the system is dimensioned.

A connection of the Smart Line Modules connected in parallel using DRIVE-CLiQ must be taken into consideration.

For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

A 4 % reactor is always required upstream of each Smart Line Module for the purpose of current symmetrization. This is integrated as standard. Just as with the Basic Line Modules, "mirror-image" power connections are available for Smart Line Modules, which enable parallel circuits to be realized in a compact design. Units that are arranged to the left of the Line Connection Module have the letter "C" at the next to last position of the order number. Example: 6SL3730-6TE41-1BC3 (see also the corresponding diagram for the Basic Line Modules).

Интеграция



Connection example of a Smart Line Module

Опции



The table below lists the options available for Smart Line Modules (Details → Description of the options):

Available options

Order code

CBC10 Communication Board

G20 1)

CBE20 Communication Board

G33 1)

AOP30 Advanced Operator Panel installed in the cabinet door

K08 1)

CU320-2 DP Control Unit

K90

Performance expansion for CU320-2

K94 1)

Control Unit CU320‑2 PN

K95

Scope of delivery without line reactor

L22

Cabinet anti-condensation heating

L55

50/250 kW braking unit (can be used for frame size GB/GD) for line voltages of 380 … 480 V and 660 … 690 V

L62

50/250 kW braking unit (can be used for frame size GB/GD) for line voltages of 500 … 600 V

L65

Base 100 mm high, RAL 7022

M06

Cable-marshalling space 200 mm high, RAL 7035

M07

IP21 degree of protection

M21

IP23 degree of protection (includes M60)

M23

Side panel mounted at the right

M26

Side panel mounted at the left

M27

IP43 degree of protection (includes M60)

M43

IP54 degree of protection (includes M60)

M54

Closed cabinet door, air intake from below through floor opening

M59

Additional touch protection (included in M23, M43 and M54)

M60

DC busbar system (Id = 1170 A, 1 × 60 × 10 mm)

M80

DC busbar system (Id = 1500 A, 1 × 80 × 10 mm)

M81

DC busbar system (Id = 1840 A, 1 × 100 × 10 mm)

M82

DC busbar system (Id = 2150 A, 2 × 60 × 10 mm)

M83

DC busbar system (Id = 2730 A, 2 × 80 × 10 mm)

M84

DC busbar system (Id = 3320 A, 2 × 100 × 10 mm)

M85

DC busbar system (Id = 3720 A, 3 × 80 × 10 mm)

M86

DC busbar system (Id = 4480 A, 3 × 100 × 10 mm)

M87

Crane transport assembly (top-mounted)

M90

Special paint finish for cabinet

Y09

Factory assembly as transport units

Y11

One-line label for system identification, 40 × 80 mm

Y31

Two-line label for system identification, 40 × 180 mm

Y32

Four-line label for system identification, 40 × 180 mm

Y33

Customer documentation (circuit diagram, erminal diagram, layout diagram) in DXF format

D02

Preliminary version of customer documentation in PDF format

D14

Documentation in English/French

D58

Documentation in English/Spanish

D60

Documentation in English/Italian

D80

Without Operating Instructions

D99

Rating plate data in English/French

T58

Rating plate data in English/Spanish

T60

Rating plate data in English/Italian

T80

Visual acceptance

F03

Function test without connected motor

F71

Insulation test

F77

Customer-specific acceptance inspections (on request)

F97



1) Only together with option K90 or K95.

Option selection matrix for Smart Line Modules

Certain options can mutually exclude one another
(options that are not involved are not shown).

Possible combination

Combination not possible



Electrical options

 

G20

G33

K90

K95

G20

 

G33

 

K90

 

K95

 



Mechanical/electrical options

 

M06

M07

M21

M23

M26

M27

M43

M54

M60

M90

Y11

Y31

Y32

Y33

M06

 

M07

 

M21

 

M23

 

– 1)

M26

 

M27

 

M43

 

– 1)

M54

 

– 1)

M60

– 1)

– 1)

– 1)

 

M90

 

Y11

 

Y31

 

Y32

 

Y33

 



1) The option M60 is included in M23, M43 and M54.

DC busbar system mechanical options (busbars between individual Cabinet Modules)

 

M80

M81

M82

M83

M84

M85

M86

M87

M80

 

M81

 

M82

 

M83

 

M84

 

M85

 

M86

 

M87

 



Docu­mentation

 

D02

D14

D58

D60

D80

D99

D02

 

D14

 

D58

 

D60

 

D80

 

D99

 



Rating plate data

 

T58

T60

T80

T58

 

T60

 

T80

 



Технические данные



Line voltage 380 … 480 V 3 AC

Smart Line Modules

 

6SL3730-6TE35-5AA3

6SL3730-6TE37-3AA3

6SL3730-6TE41-1AA3

6SL3730-6TE41-3AA3

6SL3730-6TE41-7AA3

For a parallel circuit configuration, mounted to the right at the Line Connection Module

 

 

6SL3730-6TE41-1BA3

6SL3730-6TE41-3BA3

6SL3730-6TE41-7BA3

For a parallel circuit configuration, mounted to the left at the Line Connection Module

 

 

6SL3730-6TE41-1BC3

6SL3730-6TE41-3BC3

6SL3730-6TE41-7BC3

Rated power

      
  • For IN DC (50 Hz 400 V)

kW

250

355

500

630

800

  • For IH DC (50 Hz 400 V)

kW

235

315

450

555

730

  • For IN DC (60 Hz 460 V)

hp

395

545

770

970

1230

  • For IH DC (60 Hz 460 V)

hp

360

485

695

855

1125

DC link current

      
  • Rated current IN DC

A

550

730

1050

1300

1700

  • Base load current IH DC 1)

A

490

650

934

1157

1513

  • Maximum current Imax DC

A

825

1095

1575

1950

2550

Infeed/regenerative feedback current

      
  • Rated current IN E

A

463

614

883

1093

1430

  • Maximum current Imax E

A

694

921

1324

1639

2145

Current demand

      
  • 24 V DC auxiliary power supply

A

1.35

1.35

1.4

1.5

1.7

  • 400 V AC 2)

A

1.8

1.8

3.6

5.4

5.4

DC link capacitance

      
  • Smart Line Module

μF

8400

12000

16800

18900

28800

  • Drive line-up, max.

μF

42000

60000

67200

75600

115200

Power loss, max. 3)

      
  • At 50 Hz 400 V

kW

3.7

4.7

7.1

11.0

11.5

  • At 60 Hz 460 V

kW

3.7

4.7

7.1

11.0

11.5

Cooling air requirement

m3/s

0.36

0.36

0.78

1.08

1.08

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

69/73

69/73

70/73

70/73

70/73

PE/GND connection

 

PE bar

PE bar

PE bar

PE bar

PE bar

  • Busbar cross-section

mm2

600

600

600

600

600

  • Conductor cross-section, max. (IEC)

mm2

240

240

240

240

240

Cable length, max. 4)

      
  • Shielded

m

4000

4000

4800

4800

4800

  • Unshielded

m

6000

6000

7200

7200

7200

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

      
  • Width

mm

400

400

600

800

800

  • Height 5)

mm

2200

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

600

Weight, approx.

kg

270

270

490

775

775

Frame size

 

GX

GX

HX

JX

JX



1) The base load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

2) The current demand for the 400 V AC auxiliary power supply is drawn from the line input voltage.

3) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

4) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request.

5) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23, IP43, IP54 degrees of protection.

Line voltage 500 … 690 V 3 AC

Smart Line Modules

 

6SL3730-6TG35-5AA3

6SL3730-6TG38-8AA3

6SL3730-6TG41-2AA3

6SL3730-6TG41-7AA3

For a parallel circuit configuration, mounted to the right at the Line Connection Module

 

6SL3730-6TG38-8BA3

6SL3730-6TG41-2BA3

6SL3730-6TG41-7BA3

For a parallel circuit configuration, mounted to the left at the Line Connection Module

 

6SL3730-6TG38-8BC3

6SL3730-6TG41-2BC3

6SL3730-6TG41-7BC3

Rated power

     
  • For IN DC (50 Hz 690 V)

kW

450

710

1000

1400

  • For IH DC (50 Hz 690 V)

kW

405

665

885

1255

  • For IN DC (50 Hz 500 V)

kW

Запрос коммерческого предложения

×

    * Поля, обязательные для заполнения.

    Сообщение отправлено

    ×

    В ближайшее время сообщение будет обработано.

    Письмо с номером обращения отправлено на Ваш почтовый ящик.

    Спасибо за то, что выбрали Первый ZIP!

    Что-то пошло не так...

    ×

    К сожалению, наша система расценила Ваше сообщение как спам.

    Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте.

    Приносим извинения за возможные неудобства.