Line-side components -Recommended fuses Siemens

Обзор



The fuses specified below are the recommended types for protecting the unit on the low-voltage distribution panel. If option L26 was selected for SINAMICS S150 with rated input currents < 800 A, then the semiconductor protection is already integrated in the unit. For units > 800 A, this function is realized by the circuit breaker provided as standard.
In this case, a 3NA fuse can be used in the distribution system. If option L26 has not been selected for units < 800 A, then we strongly advise that 3NE fuses are used. 1)

Catalog LV 10.1 contains additional information on the fuses that have been listed.

Type rating
at 400 V or 690 V

SINAMICS S150 converter

Cable protection fuse
in systems with fuse switch disconnector

Cable protection fuse
(incl. semiconductor protection) in systems without fuse switch disconnector

For IL, 50 Hz 400 V, 500 V or 690 V

For IL, 60 Hz 460 V or 575 V

 

 

Rated current

Frame size acc. to DIN 43620‑1

 

Rated current

Frame size acc. to DIN 43620‑1

kW

hp

6SL3710-...

Order No.

A

 

Order No.

A

 

Line voltage 380 … 480 V 3 AC

110

150

7LE32-1AA3

3NA3252

315

2

3NE1230-2

315

1

132

200

7LE32-6AA3

3NA3254

355

2

3NE1331-2

350

2

160

250

7LE33-1AA3

3NA3365

500

3

3NE1334-2

500

2

200

300

7LE33-8AA3

3NA3365

500

3

3NE1334-2

500

2

250

400

7LE35-0AA3

3NA3372

630

3

3NE1436-2

630

3

315

500

7LE36-1AA3

3NA3475

800

4

3NE1438-2

800

3

400

600

7LE37-5AA3

3NA3475

800

4

3NE1448-2

850

3

450

700

7LE38-4AA3

Circuit breaker included as standard

560

800

7LE41-0AA3

Circuit breaker included as standard

710

1000

7LE41-2AA3

Circuit breaker included as standard

800

1000

7LE41-4AA3

Circuit breaker included as standard

Line voltage 500 ... 690 V 3 AC

75

75

7LG28-5AA3

3NA3132-6

125

1

3NE1022-2

125

00

90

75

7LG31-0AA3

3NA3132-6

125

1

3NE1022-2

125

00

110

100

7LG31-2AA3

3NA3136-6

160

1

3NE1224-2

160

1

132

150

7LG31-5AA3

3NA3240-6

200

2

3NE1225-2

200

1

160

150

7LG31-8AA3

3NA3244-6

250

2

3NE1227-2

250

1

200

200

7LG32-2AA3

3NA3252-6

315

2

3NE1230-2

315

1

250

250

7LG32-6AA3

3NA3354-6

355

3

3NE1331-2

350

2

315

300

7LG33-3AA3

3NA3365-6

500

3

3NE1334-2

500

2

400

400

7LG34-1AA3

3NA3365-6

500

3

3NE1334-2

500

2

450

450

7LG34-7AA3

3NA3352-6

2 × 315

2

3NE1435-2

560

3

560

600

7LG35-8AA3

3NA3354-6

2 × 355

3

3NE1447-2

670

3

710

700

7LG37-4AA3

3NA3365-6

2 × 500

3

3NE1448-2

850

3

800

800

7LG38-1AA3

Circuit breaker included as standard

900

900

7LG38-8AA3

Circuit breaker included as standard

1000

1000

7LG41-0AA3

Circuit breaker included as standard

1200

1250

7LG41-3AA3

Circuit breaker included as standard



1) The double function fuses (3NE1.) with duty class gS for cable and semiconductor protection are recommended to protect the converter. These fuses are specially adapted to the requirements of the semiconductors in the input rectifier.

- super flink

- coordinated to the I2t integral of the semiconductor

- lower arc voltage

- better current limiting (lower let-through I2t values)