CP 443-1 Siemens

Область применения


  • The CP 443-1 is used to connect the SIMATIC S7-400 to Industrial Ethernet networks. With its own processor, it relieves the CPU of communications tasks and facilitates additional connections.

The CP 443-1 offers communication options with

  • PGs/PCs
  • Host computers
  • HMI systems
  • SIMATIC S5/S7/C7 systems
  • PROFINET IO devices

Обзор



Communications processor for connecting a SIMATIC S7-400 to Industrial Ethernet networks, also as PROFINET IO controller or in SIMATIC H systems.

The CP supports:

  • PG/OP communication
  • S7 communication
  • Open communication (SEND/RECEIVE)
  • PROFINET communication
  • IT communication

The communications processor can also be used for redundant S7 communication in SIMATIC H systems and for fail-safe applications (PROFIsafe) in connection with an S7-400 F-CPU.

Дизайн



The CP 443-1 features all the advantages of the SIMATIC S7-400 design:

  • Compact design:
    • Two RJ45 sockets for connecting to Industrial Ethernet; automatic data rate detection by means of the autosensing/autocrossover function; the connection is made via the IE FC RJ45 Plug 180 with 180° cable outlet or via a standard patch cable
    • Diagnostics LEDs for indicating the operational and communication status
  • Easy installation:
    The CP 443-1 is mounted on the S7-400 rack and connected to the other modules via the backplane bus. No slot rules apply.
  • The CP 443-1 can be operated without a fan
  • The CP 443-1 can also be operated in the expansion rack (ER) in conjunction with the IM 460/461
  • The module can be replaced without the need for a programming device

Функции


  • Two RJ45 ports with 10/100 Mbps full/half duplex with autosensing and autocrossover functionality via integrated 2-port switch
  • Communication services of the interface:
    • Open communication (TCP/IP and UDP): Multicast with UDP, including routing between both interfaces
    • PG/OP communication: Inter-network with S7 routing
    • S7 communication (client, server, multiplexing) including routing between both interfaces
    • S7 H communication for S7-400 H systems, now also across network boundaries (ISO-on-TCP)
    • Certified PROFINET IO controller with real-time properties (RT and IRT)
    • IP address assignment via DHCP, simple PC tool or via program block (e.g. for HMI)
  • Media redundancy (MRP):
    • Within an Ethernet network with ring topology, the CP supports the media redundancy procedure MRPMRP as an MRP Manager and as an MRP Client
  • Diagnostics and network management:
    • Comprehensive diagnostics functions for all modules in the rack (including graphical diagnostics, e.g. topology)
    • Integration in network management systems due to support of SNMP V1/V3
  • Security mechanisms:
  • Configuration of all functions with STEP 7 V5.5 SP2;
    configuration with STEP 7 Professional V11 only with a limited range of functions of the predecessor CP 443-1 (6GK7 443-1EX20-0XE0) possible
  • When using the blocks AG_SSEND (FC53), AG_SRECV (FC63), TSEND (FB63), TRCV (FB64), TCON (FB65) and TDISCON (FB66), please note the following information: http://support.automation.siemens.com/WW/view/en/60037071
  • Module replacement without programming device: All information can be stored on the CPU

Интеграция



Interfacing to higher-level network with CP 443-1 as PROFINET IO controller

Line structure as PROFINET IO controller with integrated real-time switch

Line structure at the superordinated control level through integrated 2-port switch

Особенности


  • High plant availability through the support of media redundancy (MRP) and use in the SIMATIC S7-400 H system
  • Optimum support of maintenance through
    • Web-based diagnostics
    • Remote programming via WAN or a telephone network (ISDN)
    • Monitoring by means of IT network management tools (SNMP)
    • Module exchange without programming device using the C-PLUG swap medium
  • Securing the system against unauthorized access by means of
    • Central access protection for any devices within an automation cell, e.g. by means of authentication of the network stations
  • The capability of later connecting existing SIMATIC S7 systems to Industrial Ethernet using the CP 443-1 ensures investment protection

Технические данные



Order number

6GK7443-1EX30-0XE0

Product type designation

CP 443-1

Transmission rate

 

Transfer rate

 

  • at the 1st interface

10 ... 100 Mbit/s

Interfaces

 

Number of interfaces acc. to Industrial Ethernet

2

Number of electrical connections

 

  • at the 1st interface acc. to Industrial Ethernet

2

Type of electrical connection

 

  • at the 1st interface acc. to Industrial Ethernet

RJ45 port

design of the removable storage C-PLUG

No

Supply voltage, current consumption, power loss

 

Type of voltage of the supply voltage

DC

Supply voltage 1 from backplane bus

5 V

Relative symmetrical tolerance at DC

 

  • at 5 V

5 %

Consumed current

 

  • from backplane bus at DC at 5 V typical

1.4 A

Active power loss

7.25 W

Permitted ambient conditions

 

Ambient temperature

 

  • during operation

0 ... 60 °C

  • during storage

-40 ... +70 °C

  • during transport

-40 ... +70 °C

Relative humidity at 25 °C without condensation during operation maximum

95 %

Protection class IP

IP20

Design, dimensions and weight

 

Module format

Compact module S7-400 single width

Width

25 mm

Height

290 mm

Depth

210 mm

Net weight

0.7 kg

Product properties, functions, components general

 

Number of units

 

  • per CPU maximum

14

  • Note

max. 4 as PN IO ctrl.

Performance data open communication

 

Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum

64

Amount of data

 

  • as user data per ISO connection for open communication by means of SEND/RECEIVE blocks maximum

8 Kibyte

  • as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum

8 Kibyte

  • as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum

8 Kibyte

  • as user data per UDP connection for open IE communication by means of SEND/RECEIVE blocks maximum

2 Kibyte

Number of possible connections for open communication

 

  • by means of T blocks maximum

64

Amount of data

 

  • as user data per ISO on TCP connection for open communication by means of T blocks maximum

1 452 byte

Performance data S7 communication

 

Number of possible connections for S7 communication

 

  • maximum

128

  • with PG connections maximum

2

  • Note

when using several CPUs

Performance data multi-protocol mode

 

Number of active connections with multi-protocol mode

128

Performance data PROFINET communication as PN IO-Controller

 

Product function PROFINET IO controller

Yes

Number of PN IO devices on PROFINET IO controller usable total

128

Number of PN IO IRT devices on PROFINET IO controller usable

64

Number of external PN IO lines with PROFINET per rack

4

Amount of data

 

  • as user data for input variables as PROFINET IO controller maximum

4 Kibyte

  • as user data for input variables as PROFINET IO controller maximum

4 Kibyte

  • as user data for input variables per PN IO device as PROFINET IO controller maximum

1 433 byte

  • as user data for output variables per PN IO device as PROFINET IO controller maximum

1 433 byte

  • as user data for input variables per PN IO device for each sub-module as PROFINET IO controller maximum

240 byte

  • as user data for output variables per PN IO device for each sub-module as PROFINET IO controller maximum

240 byte

Performance data telecontrol

 

Protocol is supported

 

  • TCP/IP

Yes

Product functions management, configuration

 

Product function MIB support

Yes

Protocol is supported

 

  • SNMP v1

Yes

  • DCP

Yes

  • LLDP

Yes

Configuration software

 

  • required

STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher

Product functions Diagnosis

 

Product function Web-based diagnostics

Yes

Product functions switch

 

Product feature Switch

Yes

Product function

 

  • switch-managed

No

  • with IRT PROFINET IO switch

Yes

  • Configuration with STEP 7

Yes

Product functions Redundancy

 

Product function

 

  • Ring redundancy

Yes

  • Redundancy manager

Yes

Protocol is supported Media Redundancy Protocol (MRP)

Yes

Product functions Security

 

Product function

 

  • password protection for Web applications

No

  • ACL - IP-based

Yes

  • ACL - IP-based for PLC/routing

No

  • switch-off of non-required services

Yes

  • Blocking of communication via physical ports

Yes

  • log file for unauthorized access

No

Product functions Time

 

Product function SICLOCK support

Yes

Product function pass on time synchronization

Yes

Protocol is supported NTP

Yes