Область применения
The IM 461-0 interface module is intended for use as a send IM for central connection over short distances of up to 5 m. It receives data from both the P-bus and the C-bus.
The IM 461-0 interface module is intended for use only in association with the IM 460-0 interface module (in the central controller).
Обзор
- Receive interface connection for central extension up to 5 m
- Transfer from P and K Bus
- Pluggable in extension device
- Usable exclusively with IM 460-0
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
Дизайн
The IM 461-0 interface module can be inserted into the following expansion modules:
- UR1,
- UR2,
- ER1 and
- ER2.
The module has:
- 2 LEDs for indicating faults.
- 1 interface (input) for connecting the 468-1 connecting cable of the upstream interface module.
- 1 interface (output) for connecting the 468-1 cable to the downstream interface module. At the last interface module on the line, a terminating connector must be plugged into this interface.
- Coding switch for setting the number of the rack.
- Battery infeed socket for connecting an external battery when replacing the rack power supply.
Технические данные
Order number | 6AG1461-0AA01-2AA0 | |
|---|---|---|
SIPLUS S7-400 IM461-0 RX | ||
Input current |
| |
from backplane bus 5 V DC, max. | 290 mA | |
Power loss |
| |
Power loss, max. | 1 450 mW | |
Hardware configuration |
| |
Cable length between first and last interface module, max. | 5 m | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| -25 °C; = Tmin | |
| 60 °C; = Tmax | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance |
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions |
| |
Width | 25 mm | |
Height | 290 mm | |
Depth | 217 mm | |
Weights |
| |
Weight, approx. | 610 g | |