SIPLUS S7-400 interface modules Siemens

Обзор
- To connect distributed I/O via PROFIBUS DP
- Max. transmission rate 12 Mbit/s
- Electrically isolated RS-485 interface
- Connection via 9-pin Sub-D socket
- One or two PROFIBUS modules can be plugged in for each S7-400 CPU:
- CPU 414-3/416-3: 1 module
- CPU 417-4: 2 modules
Notes:
Can only be used with the CPUs 6AG1 416-3XR05-4AB0, 6AG1 416-3ER05-4AB0 and 6AG1 417-4XT05-4AB0.
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
Технические данные
Order number | 6AG1964-2AA04-7AB0 | |
|---|---|---|
SIPLUS S7-400 IF964-DP | ||
Input current |
| |
from CPU, max. | 150 mA; Current consumption from S7-400 bus: The module uses no current at 24 V, it provides this voltage only at the DP interface. Total current consumption of the components connected to the DP interface, but maximum 150 mA. Current carrying capacity of the isolated 5 V (P5ext) maximum 90 mA, current carrying capacity of the 24 V maximum 150 mA. | |
Power loss |
| |
Power loss, typ. | 1 W | |
Interfaces |
| |
PROFIBUS DP |
| |
Cable length |
| |
| 1 200 m; At 9.6 kbit/s: max. 1200 m; at 12 Mbit/s: max. 100 m | |
1. Interface |
| |
Physics | RS 485 | |
Isolated | Yes | |
Functionality |
| |
| Yes; Default setting | |
| Yes | |
DP master |
| |
| 9.6 kbit/s | |
| 12 Mbit/s | |
| 125; depending on the CPU used | |
Services |
| |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Address area |
| |
| device-dependent | |
| device-dependent | |
User data per DP slave |
| |
| 244 byte | |
| 244 byte | |
Communication functions |
| |
Number of connections |
| |
| device-dependent | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| -25 °C; = Tmin | |
| 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
| |
| 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance |
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions |
| |
Width | 26 mm | |
Height | 54 mm | |
Depth | 130 mm | |
Weights |
| |
Weight, approx. | 65 g | |