SIPLUS S7-400 SM 421 digital input modules Siemens

Область применения
Digital input modules can be used to connect the control to digital process signals. They are suitable for connecting standard switches and two-wire proximity switches (BERO).
Обзор
- Digital inputs for SIMATIC S7-400
- For connection of switches and 2-wire proximity switches (BEROs)
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
Дизайн
The digital input modules have the following mechanical features:
- Compact configuration:
The rugged plastic housing contains:- Green LEDs to indicate signal states at the inputs
- One red LED each to indicate internal and external faults or errors in modules with diagnostic and process interrupts
- Labeling strips
- Simple assembly
- User-friendly wiring:
The modules are wired by means of a plug-in front connector.
Функции
Digital input modules convert the levels of the external digital signals from the process into the internal signal level of the S7-400.
Технические данные
Order number | 6AG1421-1BL01-2AA0 | |
|---|---|---|
SIPLUS S7-400 SM421 32DE | ||
Input current |
| |
from backplane bus 5 V DC, max. | 20 mA | |
Power loss |
| |
Power loss, typ. | 6 W | |
Digital inputs |
| |
Number of digital inputs | 32 | |
Number of simultaneously controllable inputs |
| |
| 32 | |
Input voltage |
| |
| DC | |
| 24 V | |
| -30V DC to +5V DC | |
| 13 V DC to 30 V DC | |
Input current |
| |
| 1.3 mA | |
| 7 mA | |
Cable length |
| |
| 1 000 m | |
| 600 m | |
Encoder |
| |
Connectable encoders |
| |
| Yes | |
| 1.5 mA | |
Potential separation |
| |
Potential separation digital inputs |
| |
| 32 | |
| Yes | |
Isolation |
| |
Isolation tested with | 500 V DC | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| -25 °C; = Tmin | |
| 60 °C; = Tmax | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
| |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance |
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | |
Dimensions |
| |
Width | 25 mm | |
Height | 290 mm | |
Depth | 210 mm | |
Weights |
| |
Weight, approx. | 500 g | |