SIPLUS sync module for connecting the CPU 41xH Siemens

Область применения
The Sync module is required for connecting the two CPU 41x-4H in the S7-400H subunits.
Обзор
- For linking the two CPUs 41x-5H in the subunits of the S7-400H
- Can be plugged directly into the CPU
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Дизайн
The Sync module is plugged directly into the slot of the CPU 41x-4H reserved for it. Two Sync modules are required for each CPU. Modules in the subunits are connected by means of fiber-optic connecting cables.
Технические данные
Order number | 6AG1960-1AA06-7XA0 | 6AG1960-1AB06-7XA0 | |
|---|---|---|---|
SIPLUS S7-400H IF960-H 10M | SIPLUS S7-400H IF960-H 10KM | ||
Input current |
|
| |
from CPU, max. | 220 mA | 240 mA | |
Power loss |
|
| |
Power loss, typ. | 0.77 W | 0.83 W | |
Ambient conditions |
|
| |
Ambient temperature during operation |
|
| |
| -25 °C; = Tmin | -25 °C; = Tmin | |
| 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use | 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use | |
Extended ambient conditions |
|
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
|
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance |
|
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions |
|
| |
Width | 13 mm | 13 mm | |
Height | 14 mm | 14 mm | |
Depth | 58 mm | 58 mm | |
Weights |
|
| |
Weight, approx. | 14 g | 14 g | |