Monitoring devices DOLD
Insulation monitors (20)
Fault annunciators (26)
Accessories (5)
• Monitoring of 50 - and 60 Hz-current supply on
over- and underfrequency
• Monitoring of local generator sets and voltage supplies
• For precise frequency measuring with fast response time
• High disturbance immunity
• Separately adjustable trip points and separate outputs for overand
underfrequency (1 or 2 c/o each)
• MK 9143N / MH 9143:
- Trip points adjustable precisely and reproducible on 10 step
rotational switch in the range of ± 0,1 Hz to ± 5 Hz related to
50 or 60 Hz
- Nominal frequency 50 or 60 Hz selectable
- Fixed hysteresis optimised for trip point
- Time delay for over and underfrequency each adjustable
from 0 to 20 s
- As option one common output for under and overfrequency
“Window”-mode (MK 9143N/400 / MH 9143/400)
• MH 9143.38/008: with galvanic separated analogue output (current/
voltage) and 11 step LED chain for the actual frequency
• MK 9143N/600 / MH 9143/600:
- Variable alarm value in the range of 45 to 65 Hz
- Hysteresis adjustable for under- and overfrequency separately
adjustable 0 …20%
- Common output for under and overfrequency “Window”-mode
can be selected
• Start up delay 0…30 s selectable
• Manual or auto reset selectable
• Output relay energized or de-energized on trip selectable for
overfrequency
• Output relay de-energized on trip for underfrequency
• Universal frequency measuring input for AC 40 … 550V
• Several options for auxiliary supply
• As option without aux. supply for voltage range AC 18 … 70 V or
70 … 275V
• LED indicators for auxiliary supply, input frequency, over and
under frequency alarm
• 2 possible contact arrangements
MK 9143N and MK 9143N/600: 2 x 1 C/O contacts, width 22,5 mm
MH 9143 and MH 9143/600: 2 x 2 C/O contacts, width 45 mm
• Monitoring of AC voltage for under and overfrequency,
can be used also for pre-warning
• Separate relay outputs for over- or underfrequency
(1 or 2 changeover contacts each)
• Alternative usage for monitoring of a frequency window
• Separate adjustment of response value for over- or underfrequency
at 4 ranges each, 1.5 ... 200 Hz or 5 ... 600 Hz
• Second response value for prewarning possible
• Fast reaction time by measuring duration of cycle of input frequency
• Universal measuring input for AC-voltages of 15 ... 280 V
as well as 30 ... 550 V
• As option with measuring input for inverters
• Programmable hysteresis of response value: 2 ... 10 %
• Start up time delay programmable via terminals from
0 ... 50 s e.g. continuously
• Manual or auto-reset programmable via terminals
• Galvanic separation between measuring input, auxiliary voltage
and output contacts
• MH 9837/508: with galvanic separated analogue output (current/
voltage) and 11 step LED chain for the actual frequency
• MH 9837/5_0: with wide input range for auxiliary voltage available
(AC/DC 24 ... 60 V or AC/DC 110 ... 230 V)
• Closed circuit operation (de-energized on trip)
• LED indication for auxiliary voltage, measuring voltage and
alarm status
• Device available with 2 contacts
MK 9837N/5_0: 2 x 1 changeover contact
MH 9837/5_0: 2 x 2 changeover contacts or
wide auxiliary voltage range
• 2 possible compact designs:
MK 9837N/5_0: Width 22,5 mm
MH 9837/5_0: Width 45 mm
• Surveillance en sous et surfréquence de réseaux 50/60Hz
• Surveillance de groupes et générateurs électriques
• Mesure de fréquence précise et rapide
• Entrée de mesure fortement protégée
• 2 seuils d’alarme séparés pour sous et surfréquence avec des
sorties relais séparées. (1 ou 2 inverseurs pour chaque relais)
• MK 9143N / MH 9143:
- Seuils d’alarme réglables précisément au travers d’un
commutateur 10 positions pour des plages de + 0,1 à + 5 Hz
de la fréquence de référence
- Fréquance de référence commutable de 50 à 60 Hz
- Hysterese fixe adaptée au seuil de réglage
- Temporisations d’alarme pour la sous et la surfréquence
réglables séparément de 0-20s.
- Sur demande, avec relais de sortie rágissant en mode“
Windows“ (à l’intérieur d’une fenêtre de fréquence)
(MK 9143N/400 / MH 9143/400)
• MH 9143.38/008: avec sortie analogique séparée galvaniquement
ainsi qu'une barre de visualisation à 11 LED pour l'indication de la
valeur actuelle de l'isolement
• MK 9143N/600 / MH 9143/600:
- Seuil d’alarme réglable dans une plage de 45-65Hz
- Hystérèse réglable séparément pour le seuil de sous et
surfréquence de 0,5-20%
- Mode de fonctionnement Window du relais de sortie
programmable (fenêtre de fréquence)
• Temporisation de démarrage configurable sur bornier dans la
plage de 0-30s
• Fonction Mémorisation ou hystérése de l’alarme configurable sur bornier
• Relais de sortie pour la surtension réglable en fonction de repos ou
de travail
• Relais de sortie pour la sous-tension en fonction de repos
(retombe en cas de sous-fréquence)
• Entrée de mesure de fréquence universel pour tensions de 40-550V
• Livrable pour diverses tensions d’alimentations
• Sur demande sans alimentation auxiliaire pour une plage de tension
de AC 18-70 ou 70-275V
• DEL de visualisation pour l’alimentation, la présence de signal
d’entrée, la sous et la surfréquence
• MH 9143.38/008: sortie analogique et une barre de visualisation pour
l'indication de la valeur actuelle de l'isolement
• 2 versions au choix:
MK 9143N et MK 9143N/600: 2 x 1 INV, Largeur utile 22,5 mm
MH 9143 et MH 9143/600: 2 x 2 INV, Largeur utile 45 mm
• Recognizes fuse failures in three-phase mains up to 3 AC 690 V
• Can be used for all types and sizes of fuses
• Independent of phase sequence
• Signals even if loads are switched off
• No malfunction on
- asymmetrical mains
- mains with harmonic waves
- motors producing feedback
• Shorter response time than with motor circuit-breakers
• Green LED for intact fuses
• Red LED for fuse failure
• As option: open/closed circuit operation in the case
of IP 9075 programmable via X4-X5 or X3-X4
• As option: with manual reset function and remote reset,
programmable via X1-X2
• As option: 1 NO contact or 2 changeover contacts
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• IL 9075, SL 9075: width 35 mm
IP 9075, SP 9075: width 70 mm
• Monitoring of AC voltage for under and overfrequency,
can be used also for pre-warning
• Separate relay outputs for over- or underfrequency
(1 or 2 changeover contacts each)
• Alternative usage for monitoring of a frequency window
• Separate adjustment of response value for over- or underfrequency
at 4 ranges each, 1.5 ... 200 Hz or 5 ... 600 Hz
• Second response value for prewarning possible
• Fast reaction time by measuring duration of cycle of input frequency
• Universal measuring input for AC-voltages of 15 ... 280 V
as well as 30 ... 550 V
• As option with measuring input for inverters
• Programmable hysteresis of response value: 2 ... 10 %
• Start up time delay programmable via terminals from
0 ... 50 s e.g. continuously
• Manual or auto-reset programmable via terminals
• Galvanic separation between measuring input, auxiliary voltage
and output contacts
• MH 9837/508: with galvanic separated analogue output (current/
voltage) and 11 step LED chain for the actual frequency
• MH 9837/5_0: with wide input range for auxiliary voltage available
(AC/DC 24 ... 60 V or AC/DC 110 ... 230 V)
• Closed circuit operation (de-energized on trip)
• LED indication for auxiliary voltage, measuring voltage and
alarm status
• Device available with 2 contacts
MK 9837N/5_0: 2 x 1 changeover contact
MH 9837/5_0: 2 x 2 changeover contacts or
wide auxiliary voltage range
• 2 possible compact designs:
MK 9837N/5_0: Width 22,5 mm
MH 9837/5_0: Width 45 mm
• Recognizes fuse failures in three-phase mains up to 3 AC 690 V
• Can be used for all types and sizes of fuses
• Independent of phase sequence
• Signals even if loads are switched off
• No malfunction on
- asymmetrical mains
- mains with harmonic waves
- motors producing feedback
• Shorter response time than with motor circuit-breakers
• Green LED for intact fuses
• Red LED for fuse failure
• As option: open/closed circuit operation in the case
of IP 9075 programmable via X4-X5 or X3-X4
• As option: with manual reset function and remote reset,
programmable via X1-X2
• As option: 1 NO contact or 2 changeover contacts
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• IL 9075, SL 9075: width 35 mm
IP 9075, SP 9075: width 70 mm
• Detection of under- or overfrequency
• Adjustable response value
• Optionally 1 or 2 changeover contacts
• Width 45 mm
• Recognizes fuse failures in three-phase mains up to 3 AC 690 V
• Can be used for all types and sizes of fuses
• Independent of phase sequence
• Signals even if loads are switched off
• No malfunction on
- asymmetrical mains
- mains with harmonic waves
- motors producing feedback
• Shorter response time than with motor circuit-breakers
• Green LED for intact fuses
• Red LED for fuse failure
• As option: open/closed circuit operation in the case
of IP 9075 programmable via X4-X5 or X3-X4
• As option: with manual reset function and remote reset,
programmable via X1-X2
• As option: 1 NO contact or 2 changeover contacts
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• IL 9075, SL 9075: width 35 mm
IP 9075, SP 9075: width 70 mm
• Detection of over- or underfrequency of alternating voltage
(adjustable function)
• Fast reaction time by measuring duration of cycle of input frequency
• Universal measuring input for AC-voltages of 15 ... 280 V
as well as 30 ... 550 V
• As option with measuring input for inverters
• 4 ranges adjustable response value 1,5 ... 200 Hz or 5 ... 600 Hz
• Adjustable hysteresis
• Adjustable start up time delay 0 ... 50 s at function underfrequency
• Adjustable monitoring time for missing input signal at function
overfrequency
• Response delay programmable via terminals 0 ... 100 s
• Alarm storing or auto-reset programmable via terminals
• Galvanic separation between measuring input, auxiliary voltage
and output contacts
• MH 9837 available with wide input range for auxiliary supply
(AC/DC 24 ... 60 V or AC/DC 110 ... 230 V)
• 2 changeover contacts, closed circuit operation
• Open circuit operation on request
• LED indication for auxiliary voltage, measuring voltage and
alarm status
• MH 9837.12/008: with galvanic separated analogue output (current/
voltage) and 11 step LED chain for the actual frequency
• Device available with 2 response values and seperately controlled
outputrelays for under- and overfrequency see MK 9837N/500
• 2 possible compact designs:
MK 9837N: Width 22,5 mm
MH 9837: Width 45 mm
• To monitor fuses in single and 3-phase AC voltage systems
• Undervoltage detection below 0.7 x UN
• No separate auxiliary necessary
• 2 changeover contacts
• 2 nominal voltages adjustable:
3/N AC 240 V / 140 V or 3/N AC400 V / 230 V or
fixed nominal voltage: 3/N AC 110 V / 64 V
• Adjustable operate delay
• Energized on trip
• Automatic adjustment to 50 Hz and 60 Hz mains frequency
• Width 22.5 mm
• Recognizes fuse failures in three-phase mains up to 3 AC 690 V
• Can be used for all types and sizes of fuses
• Independent of phase sequence
• Signals even if loads are switched off
• No malfunction on
- asymmetrical mains
- mains with harmonic waves
- motors producing feedback
• Shorter response time than with motor circuit-breakers
• Green LED for intact fuses
• Red LED for fuse failure
• As option: open/closed circuit operation in the case
of IP 9075 programmable via X4-X5 or X3-X4
• As option: with manual reset function and remote reset,
programmable via X1-X2
• As option: 1 NO contact or 2 changeover contacts
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• IL 9075, SL 9075: width 35 mm
IP 9075, SP 9075: width 70 mm
• Detection of under- or overfrequency
• Adjustable response value
• Optionally 1 or 2 changeover contacts
• Width 45 mm
• Detection of over- or underfrequency of alternating voltage
(adjustable function)
• Fast reaction time by measuring duration of cycle of input frequency
• Universal measuring input for AC-voltages of 15 ... 280 V
as well as 30 ... 550 V
• As option with measuring input for inverters
• 4 ranges adjustable response value 1,5 ... 200 Hz or 5 ... 600 Hz
• Adjustable hysteresis
• Adjustable start up time delay 0 ... 50 s at function underfrequency
• Adjustable monitoring time for missing input signal at function
overfrequency
• Response delay programmable via terminals 0 ... 100 s
• Alarm storing or auto-reset programmable via terminals
• Galvanic separation between measuring input, auxiliary voltage
and output contacts
• MH 9837 available with wide input range for auxiliary supply
(AC/DC 24 ... 60 V or AC/DC 110 ... 230 V)
• 2 changeover contacts, closed circuit operation
• Open circuit operation on request
• LED indication for auxiliary voltage, measuring voltage and
alarm status
• MH 9837.12/008: with galvanic separated analogue output (current/
voltage) and 11 step LED chain for the actual frequency
• Device available with 2 response values and seperately controlled
outputrelays for under- and overfrequency see MK 9837N/500
• 2 possible compact designs:
MK 9837N: Width 22,5 mm
MH 9837: Width 45 mm
• Detection of
-- missing neutral in the system
-- broken neutral on IL/SL 9069
-- neutral exchanged against phase
• Detection of phase failure also with disconnected load
• For 3-phase systems
• De-energized on trip
• LED indicator for operation/state of output contacts
• Single phase connection possible
• Without auxiliary voltage
• 2 cangeover contacts
• Optionally with adjustable asymmetry detection and on delay
• Devices available in 2 enclosure version:
IL 9069: depth 59 mm with terminals at the bottom for
installations systems and industrial distribution
systems according to DIN 43 880
SL 9069: depth 98 mm with terminals at the top for
cabinets with mounting plate and cable duct
• Width 35 mm
• Monitoring of overfrequency and underfrequency (selectable)
in A.C. power systems
• Without auxiliary voltage
• Selection of frequency range for 50 or 60 Hz systems
• Adjustable response value
• Adjustable hysteresis
• De-energized on trip (output relay not activated in case of error)
• LED indicators for measuring voltage and contact position
• 1 changeover contact
• As option energized on trip (output relay activated in case of error)
• Devices available in 2 enclosure versions:
IK 9143: depth 58 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SK 9143: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• 17.5 mm width
• Detection of
-- missing neutral in the system
-- broken neutral on IL/SL 9069
-- neutral exchanged against phase
• Detection of phase failure also with disconnected load
• For 3-phase systems
• De-energized on trip
• LED indicator for operation/state of output contacts
• Single phase connection possible
• Without auxiliary voltage
• 2 cangeover contacts
• Optionally with adjustable asymmetry detection and on delay
• Devices available in 2 enclosure version:
IL 9069: depth 59 mm with terminals at the bottom for
installations systems and industrial distribution
systems according to DIN 43 880
SL 9069: depth 98 mm with terminals at the top for
cabinets with mounting plate and cable duct
• Width 35 mm
• Overfrequency or underfrequency monitoring of AC voltages
• Adjustable response value fmin. or fmax 5 ... 200 Hz or 15 ... 600 Hz
• Adjustable hysteresis
• Large voltage range of the measuring input (nominal voltage
AC 24 ... 440 V)
• De-energized on trip
• LED indication for auxiliary voltage, measuring voltage and contact
position
• 1 changeover contact
• As option for frequency inverters with a range of 1 … 300 Hz
• 2 changeover contacts available on request
• As option adjustable start-up delay available
• Energized on trip function available on request
• Devices available in 2 enclosure versions:
IL 9837: depth 58 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SL 9837: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• 35 mm width
• Monitoring of overfrequency and underfrequency (selectable)
in A.C. power systems
• Without auxiliary voltage
• Selection of frequency range for 50 or 60 Hz systems
• Adjustable response value
• Adjustable hysteresis
• De-energized on trip (output relay not activated in case of error)
• LED indicators for measuring voltage and contact position
• 1 changeover contact
• As option energized on trip (output relay activated in case of error)
• Devices available in 2 enclosure versions:
IK 9143: depth 58 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SK 9143: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• 17.5 mm width
• Overfrequency or underfrequency monitoring of AC voltages
• Adjustable response value fmin. or fmax 5 ... 200 Hz or 15 ... 600 Hz
• Adjustable hysteresis
• Large voltage range of the measuring input (nominal voltage
AC 24 ... 440 V)
• De-energized on trip
• LED indication for auxiliary voltage, measuring voltage and contact
position
• 1 changeover contact
• As option for frequency inverters with a range of 1 … 300 Hz
• 2 changeover contacts available on request
• As option adjustable start-up delay available
• Energized on trip function available on request
• Devices available in 2 enclosure versions:
IL 9837: depth 58 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SL 9837: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• 35 mm width
and part 303
• 1 input for PTC-resistors or bimetal contacts
• Broken wire detection in sensor circuit
• Optionally with no voltage reclosing interlock
• Closed circuit operation
• 1 or 2 changeover contacts
• Width 45 mm

Early detection of critical limit value violations
DOLD offers you a comprehensive offer of measuring and monitoring relays for your individual needs. The devices detect and provide early notification if critical limits of electrical variables such as current, voltage, power, insulation resistance, et cetera are violated. This allows dangers to people and machinery to be reliably avoided. In addition, the availability of your machines and systems will be increased and production outages will be minimised. DOLD's portfolio ranges from standard devices for the monitoring of individual variables to multifunctional devices to flexible error message systems.