Monitoring devices DOLD
Insulation monitors (20)
Fault annunciators (26)
Accessories (5)
• IP 9278, SP 9278: 3-phase
• Measuring range IP 9278, SP 9278: up to 15 A
SP 9278CT: up to 100 A
• 2 changeover contacts
• Adjustable asymmetry
• Settable time delay
• Open circuit operation
• LED indicators
• With auxiliary voltage
• Auxiliary supply and measuring input galvanic separated
• As option with external remote reset
• Width 70 mm
• IP 9277, SP 9277, SP 9277CT: 3-phase
IL 9277, SL 9277, SL 9277CT: singele phase
• Detects over- and undercurrent
• Measuring ranges from 0.1 ... 15 A
• With built in current transformer for 0.5 ... 100 A
• IL 9277, SL 9277 with 4 programmable ranges
• Settable 0.1 ... 1 IN
• Separate setting for over- and undercurrent
• Fixed hysteresis approx. 4 %
• Settable time delay
• IP 9277, SP 9277 with separate settable time delay for
over- and undercurrent
• De-energized on trip
• LED indicators for over-, under- and normal current
• Auxiliary supply and measuring input galvanic separated
• IL 9277, SL 9277 with one output relay for over- and
undercurrent
• IP 9277, SP 9277 with separate output relays for over- and
undercurrent
• Optionally energized on trip
• Devices available in 2 enclosure versions:
-- I-model, e.g. IL _ _ _ _, depth 61 mm
with terminals at the bottom for installations systems
and industrial distribution systems according to DIN 43 880
-- S-model, e.g. SL _ _ _ _, depth 100 mm
with terminals at the top for cabinets with mounting plate
and cable duct
• DIN rail or screw mounting
• Width IL 9277, SL 9277, SL 9277CT: 35 mm
IP 9277, SP 9277, SP 9277CT: 70 mm
• IP 9277, SP 9277, SP 9277CT: 3-phase
IL 9277, SL 9277, SL 9277CT: singele phase
• Detects over- and undercurrent
• Measuring ranges from 0.1 ... 15 A
• With built in current transformer for 0.5 ... 100 A
• IL 9277, SL 9277 with 4 programmable ranges
• Settable 0.1 ... 1 IN
• Separate setting for over- and undercurrent
• Fixed hysteresis approx. 4 %
• Settable time delay
• IP 9277, SP 9277 with separate settable time delay for
over- and undercurrent
• De-energized on trip
• LED indicators for over-, under- and normal current
• Auxiliary supply and measuring input galvanic separated
• IL 9277, SL 9277 with one output relay for over- and
undercurrent
• IP 9277, SP 9277 with separate output relays for over- and
undercurrent
• Optionally energized on trip
• Devices available in 2 enclosure versions:
-- I-model, e.g. IL _ _ _ _, depth 61 mm
with terminals at the bottom for installations systems
and industrial distribution systems according to DIN 43 880
-- S-model, e.g. SL _ _ _ _, depth 100 mm
with terminals at the top for cabinets with mounting plate
and cable duct
• DIN rail or screw mounting
• Width IL 9277, SL 9277, SL 9277CT: 35 mm
IP 9277, SP 9277, SP 9277CT: 70 mm
• IP 9278, SP 9278: 3-phase
• Measuring range IP 9278, SP 9278: up to 15 A
SP 9278CT: up to 100 A
• 2 changeover contacts
• Adjustable asymmetry
• Settable time delay
• Open circuit operation
• LED indicators
• With auxiliary voltage
• Auxiliary supply and measuring input galvanic separated
• As option with external remote reset
• Width 70 mm
(pr EN 60 947-8) and part 303
• Monitoring of
- Undervoltage 3 phase
- Phase failure
- Phase sequence
- Loss of neutral
- Phase asymmetry
- Overtemperature
- Broken wire in thermistor circuit
- Short circuit in thermistor circuit
• Without auxiliary supply
• 1 sensing input for 1 ... 6 thermistors
• LED indication
- Supply voltage
- Measuring voltage
- Temperature
• As option with manual reset on temperature fault
• 2 x 1 changeover contact
• Depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width 35 mm
• IP 9270, SP 9270CT: 3-phase
IK 9270, SK 9270, IL 9270, SL 9270CT: single phase
• Measuring ranges from 0.1 ... 100 A
• Settable response value
• Fixed hysteresis
• Settable time delay
• De-energized on trip
• As option energized on trip
• LED indicators
• With auxiliary voltage
• Auxiliary supply and measuring input galvanic separated
• Devices available in 2 enclosure versions:
-- I-model, e.g. IK _ _ _ _, depth 61 mm
with terminals at the bottom for installation systems and
industrial distribution systems according to DIN 43 880
-- S-model, e.g. SK _ _ _ _, depth 100 mm
with terminals at the top for cabinets with mounting plate
and cable duct
• Width IK 9270, SK 9270: 17.5 mm
IL 9270, SL 9270CT: 35 mm
IP 9270, SP 9270CT: 70 mm
• IP 9278, SP 9278: 3-phase
• Measuring range IP 9278, SP 9278: up to 15 A
SP 9278CT: up to 100 A
• 2 changeover contacts
• Adjustable asymmetry
• Settable time delay
• Open circuit operation
• LED indicators
• With auxiliary voltage
• Auxiliary supply and measuring input galvanic separated
• As option with external remote reset
• Width 70 mm
• Expandable from 16 up to 160 inputs
• in 2 groups of 8 inputs selectable:
- open circuit operation
- closed circuit operation
• Input voltage up to max. AC/DC 240 V
• Delayed inputs
• Exchangable front for individual scale
• Removable terminals
• Flush mounting
• Frame 72 x 144 mm
EP 5966:
• 16 inputs in control unit
• Output relay for common signal and audible alarm
• Built in and external connected pushbuttons for lamp test (LT),
acknowledgement of horn (QH) and of alarm (QS)
• Extension module with 16 inputs
• To display up to 88 fault messages with 80, 40 or 20 characters each
• Operating mode adjustable on base module RP 5994 for new, first or common alarm
• Reset buttons for individual alarm signal, audible alarm and common alarm on front side
• RS 485 bus connection, as option with galvanic separation
• Alarms and resets can be transmitted by SMS via GSM module RP 5810
• SMS communication is possible with up to 16 receivers
• Configuration of the text display via USB-Stick (acceccories OA 5996 Article-No. 0065659), therefore no laptop on site is necessary
• Real time clock
• Operating language for menus and failure text in English, German and French
• Up to 3 variable parameters in one message text
• 2 password levels for device configuration
• optionally with switchable interval- / permanent sound
and 2 pitches settable
• Width: 17.5 mm and depth: 64 mm
• Exchangable front label for individual legending
• As option galvanic separated RS458 bus
• Protection degree for front side IP 64
• Enclosure for flush mounting 96 x 96 mm
• Display unit EH 5994:
- 8 fault signal LEDs on the unit
- Reset buttons for audible alarm, common alarm and alarm signal
• Display unit EH 5995:
- 8 fault signal LEDs on the unit
- Without reset buttons
• optionally with switchable interval- / permanent sound
• Devices available in 2 enclosure versions:
- I- and-version, e.g. IK _ _ _ _ with depth 61 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43 880
- S-version, e.g. SK _ _ _ _ with depth 100 mm, with terminals at the top for cabinets with mounting plate and cable duct
• Width: 17,5 mm
• Fast localisation of failures and their causes
• Reduction of standstill times in production
• Adjustable operating modes:
New- / First signal annunciator according to DIN 19 235,
common alarm annunciator manual reset / auto reset settable
• Expandable from 8 to 88 fault signals
• Open or closed circuit operation settable
• Adjustable on delay for input signals 0 to 10 sec
• Reset buttons for audible alarm and common alarm on front side
• Connection for external reset of audible alarm, common alarm
and single alarm according to setting
• Galvanic separation to bus RS485 (optional)
• Accessories: buzzer RK 8832, display unit EH 5994, EH 5995
text display unit EH 5996, GMS-module RP 5810
• Width: 70 mm
Base module RP 5994:
- 8 fault signal inputs with indicator LED on the unit
- One relay output each for audible alarm and common alarm
- Reset buttons for audible alarm, common alarm, and single alarm
- Connection of remote reset button. Function according to setting
Extension module RP 5995:
- 8 fault signal inputs with indicator LED on the unit
- One relay output each for audible alarm and common alarm (on request)
- Reset buttons for audible alarm, common alarm, and single alarm
- Connection of remote reset button. Function according to setting
• Fast localisation of failures and their causes
• Reduction of standstill times in production
• Common alarm annunciator with manual or auto reset of faults
• Expandable from 8 to 88 fault signals
• Open or closed circuit operation settable with rotational switch on base unit and with link X1/X2 on extension units
• Adjustable on delay for input signals 0 to 10 sec
• Reset buttons for audible alarm and common alarm on front side
• Connection for external reset of audible alarm
• Galvanic separation to bus RS485 (optional)
• Accessories: buzzer RK 8832, display unit EH 5990, EH 5991
• Width: 70 mm
• Base Module RP 5990:
- 8 fault signal inputs with indicator LED on the unit
- One relay output each for audible alarm and common alarm
- Reset buttons for audible alarm and common alarm
- Connection for external reset of audible alarm
• Extension Module RP 5991:
- 8 fault signal inputs with indicator LED on the unit
- As option one relay output each for audible alarm and common alarm
- As option reset buttons for audible alarm and common alarm
• Common alarm annunciator
• Expandable from 4 up to 160 inputs
• Open circuit inputs / closed circuit inputs selectable via bridges X1-X2
• Delayed inputs up to 10 s
• Acknowledgement push button QH for external buzzer built in
• Accessories: Buzzer IK 8832, SK 8832
• Devices available in 2 enclosure versions:
I-model: depth 61 mm, with terminals at the bottom for installations systems and industrial distribution systems according to DIN 43 880
S-model: depth 100 mm, with terminals at the top for cabinets with mounting plate and cable duct
• Width 35 mm
Fault annunciator IL 5990, SL 5990:
• 4 inputs with LED on control unit
• 1 output for common signal and 1 output for audible alarm
• Optionally for up to 8 signals
• Closed circuit operation
• Optionally with open circuit operation
• With LED for each fault signal
• Inputs up to AC/DC 300 V
• With relay output for common signal
• Pushbutton for fault signal acknowledgement and function test
• Front surface 96 x 96 mm
• Common alarm annunciator
• Expandable from 4 up to 160 inputs
• Open circuit inputs / closed circuit inputs selectable via bridges X1-X2
• Delayed inputs up to 10 s
• Acknowledgement push button QH for external buzzer built in
• Accessories: Buzzer IK 8832, SK 8832
• Devices available in 2 enclosure versions:
I-model: depth 61 mm, with terminals at the bottom for installations systems and industrial distribution systems according to DIN 43 880
S-model: depth 100 mm, with terminals at the top for cabinets with mounting plate and cable duct
• Width 35 mm
Fault annunciator IL 5990, SL 5990:
• 4 inputs with LED on control unit
• 1 output for common signal and 1 output for audible alarm
• Common alarm annunciator for 12 signals
• 1 relay for common signal and horn
• Inputs up to AC/DC 230 V
• 1 connection for acknowledgement button of horn and lamp test
• Width: 45 mm
• Common alarm annunciator
• Expandable from 4 up to 160 inputs
• Open circuit inputs / closed circuit inputs selectable via bridges X1-X2
• Delayed inputs up to 10 s
• Acknowledgement push button QH for external buzzer built in
• Accessories: Buzzer IK 8832, SK 8832
• Devices available in 2 enclosure versions:
I-model: depth 61 mm, with terminals at the bottom for installations systems and industrial distribution systems according to DIN 43 880
S-model: depth 100 mm, with terminals at the top for cabinets with mounting plate and cable duct
• Width 35 mm
Extension unit IL 5991, SL 5991:
• 4 inputs with LED on control unit
• Fast localisation of failures and their causes
• Reduction of standstill times in production
• Common alarm annunciator with manual or auto reset of faults
• Expandable from 8 to 88 fault signals
• Open or closed circuit operation settable with rotational switch on base unit and with link X1/X2 on extension units
• Adjustable on delay for input signals 0 to 10 sec
• Reset buttons for audible alarm and common alarm on front side
• Connection for external reset of audible alarm
• Galvanic separation to bus RS485 (optional)
• Accessories: buzzer RK 8832, display unit EH 5990, EH 5991
• Width: 70 mm
• Base Module RP 5990:
- 8 fault signal inputs with indicator LED on the unit
- One relay output each for audible alarm and common alarm
- Reset buttons for audible alarm and common alarm
- Connection for external reset of audible alarm
• Extension Module RP 5991:
- 8 fault signal inputs with indicator LED on the unit
- As option one relay output each for audible alarm and common alarm
- As option reset buttons for audible alarm and common alarm

Early detection of critical limit value violations
DOLD offers you a comprehensive offer of measuring and monitoring relays for your individual needs. The devices detect and provide early notification if critical limits of electrical variables such as current, voltage, power, insulation resistance, et cetera are violated. This allows dangers to people and machinery to be reliably avoided. In addition, the availability of your machines and systems will be increased and production outages will be minimised. DOLD's portfolio ranges from standard devices for the monitoring of individual variables to multifunctional devices to flexible error message systems.